VIPA System SLIO
Data
Wiring procedure
Shield attachment
HB300 | FM | 050-1BB30 | en | 20-40
U
240V AC / 30V DC
max
I
10A
max
Cross section
0.08 ... 1.5mm
Stripping length 10mm
1
Pin number at the connector
2
Opening for screwdriver
3
Connection hole for wire
1.
Insert a suited screwdriver at an angel into the square opening as shown. Press
and hold the screwdriver in the opposite direction to open the contact spring.
2.
Insert the stripped end of wire into the round opening. You can use wires with a
cross section of 0.08mm
3.
By removing the screwdriver, the wire is securely fixed via the spring contact to the
terminal.
1
Shield bus carrier
2
Shield bus (10mm x 3mm)
3
Shield clamp
4
Cable shield
To attach the shield the mounting of shield bus carriers are necessary. The shield bus
carrier (available as accessory) serves to carry the shield bus to connect cable shields.
1.
Each System SLIO 8x periphery module has a carrier hole for the shield bus carrier.
Push the shield bus carrier, until they engage into the module. With a flat mounting
rail for adaptation to a flat mounting rail you may remove the spacer of the shield
bus carrier.
2.
Put your shield bus into the shield bus carrier.
2
(AWG 28 ... 16)
2
2
up to 1.5mm
Basics and mounting
Wiring 8x periphery modules
23