Hardware description

Technical data

3.3 Technical data
Order no.
Type
Module ID
Current consumption/power loss
Current consumption from backplane bus
Power loss
Technical data digital inputs
Number of inputs
Cable length, shielded
Cable length, unshielded
Rated load voltage
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)
Rated value
Input voltage for signal "0"
Input voltage for signal "1"
Input voltage hysteresis
Signal logic input
Frequency range
Input resistance
Input current for signal "1"
Connection of Two-Wire-BEROs possible
Max. permissible BERO quiescent current
Input delay of "0" to "1"
Input delay of "1" to "0"
Number of simultaneously utilizable inputs horizontal confi-
guration
Number of simultaneously utilizable inputs vertical configu-
ration
Input characteristic curve
Initial data size
Technical data digital outputs
Number of outputs
Cable length, shielded
Cable length, unshielded
Rated load voltage
Current consumption from load voltage L+ (without load)
44
050-1BB30
FM 050
08C4 388B
75 mA
0.9 W
4
100 m
-
DC 20.4...28.8 V
-
15 mA
DC 20.4...28.8 V
DC 0...5 V
DC 15...28.8 V
-
-
-
-
3 mA
ü
0.5 mA
0.8 µs
0.8 µs
4
4
IEC 61131-2, type 1
12 Byte
-
-
-
-
-