9.
ERROR CODE LIST
Error
Error Massage
Code
(D9008)
"UNIT VERIFY
31
ERR."
(Checked
continuously.)
"FUSE BREAK
32
OFF"
(Checked
continuously.)
"CONTROL-
40
BUS ERR."
"SP.UNIT
41
DOWN"
Table 9.3 Error Code List for AnACPU and A3A Board (Continue)
Detailed
Error
CPU
Code
States
(D9091)
Stop or
Current I/O module information is
Continue
different from that recognized when the
(set by
power was turned on.
parameter)
(1) The I/O module (including special
function modules) connection
became loose or the module was
disconnected during operation, or
wrong module was connected.
Stop or
There is an output module of which
Continue
fuse is blown.
(set by
parameter)
401
STOP
Due to the error of the control bus
which connects to special function
modules, the
cannot be executed.
402
If parameter I/O assignment is being
executed, special function modules are
not accessible at initial communication.
At error occurrence, the head I/O
number (upper 2 digits of 3 digits) of the
special function module that caused
error is stored at D9011.
411
Though an access was made to a
STOP
special function module at execution of
the
FROM TO
is received.
412
If parameter I/O assignment is being
executed, no response is received from
a special function module at initial
communication.
At error occurrence, the head I/O
number (upper 2 digits of 3 digits) of the
special function module that caused
error is stored at D9011.
Error and Cause
/
instruction
FROM TO
/
instruction, no response
9 - 16
Corrective Action
Read detailed error code using a
peripheral device and check or replace
the module which corresponds to the
data (I/O head number).
Or, monitor special registers D9116 to
D9123 using a peripheral device and
check or replace the modules if
corresponding data bit is "1".
(1) Check the FUSE BLOWN indicator
LED on the output module and
replace the fuse.
(2) Read detailed error code using a
peripheral device and replace the
fuse of the output module which
corresponds to the data (I/O head
number).
Or, monitor special registers D9100 to
D9107 using a peripheral device and
replace the fuse of the output module
of which corresponding data bit is "1".
Since it is a hardware error of special
function module, CPU module or base
module, replace and check defective
module(s). Consult Mitsubishi
representative for defective modules.
Since it is hardware error of the special
function module to which an access was
made, consult Mitsubishi representative.

Advertisement