AC Voltage Regulation
Frequency Ra (Synchronize range)
Frequency Range (Batt. Mode)
AC mode
Overload
Battery mode
Current Crest Ratio
Harmonic Distortion
Line
Transfer
Inverter
Time
Inverter
EFFICIENCY
AC mode
ECO Mode
Battery Mode
BATTERY
Type
Numbers
Maximum charging current*
Floating Voltage
Boost Charging
Charger Voltage Regulation
Ripple Voltage
Ripple Current (% C10)
PHYSICAL
Dimension D X W X H mm
Dual Input
Net Weight(kg)
Model
ENVIRONMENT
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
139
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 02 19 AA 59 203 07
< 1% Typical (balanced load) < 2% Typical (unbalanced load)
1 hour for 105 ~110%, 10 mins for 111~125%, 1 min for 126~150%, 200ms for
1 hour for 105 ~110%, 10 mins for 111~125%, 1 min for 126~150%, 200ms for
Battery
Synchronous transfer: <= 0ms Asynchronous transfer: < 1 cycle
Bypass
ECO
24A**
945 x 567 x 1015
197
220/230/240VAC (Ph-N)
40Hz ~ 70Hz
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
>150%
>150%
3:1 max
100% linear load: <2% 100% nonlinear load: <4%
0 ms
<20 ms
94%, Line mode @ 100% R Load
93.5%, Line mode @ 50% R Load
98%, ECO Mode @ 100% R Load
97%, ECO Mode @ 50% R Load
93 %, Battery mode @ 100% R Load
92.5%, Battery mode @ 50% R Load
Depending on applications
32 36 40 (adjustable)
32A**
2.29V/cell
2.35V/cell
< 1%
< 1%
< 5
232
40A**
48A**
995 x 567 x 1455
309
343