Step 5
Lock back the mechanical lock plate as shown below.
100KVA/120KVA

6-4. Turn off Operation

6-4-1. Turn Off Operation in Bypass Mode/ Standby Mode
When the UPS is neither turned on or off, the UPS operates in the Standby Mode or Bypass Mode,
depending on the "Bypass Mode" Setting.
The LCD diagrams are shown below.
Bypass Mode Setting is Disabled
Step 1: Switch OFF the Q1 Breaker. The LCD diagrams are shown below.
Bypass Mode Setting is Disabled
UPS enters Shutdown Mode.
Bypass Mode Setting is Enabled
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
131
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 02 19 AA 59 203 07
160KVA/200KVA
Bypass Mode Setting is Enabled
It is normal the Un-Connection is shown when