Installing The Power Extend Converter Into Adistribution Position; Important Safety Instructions; Restrictions - Vertiv eSure 60017372 Installation Manual

Power extend converter, mounting bracket and door kit
Table of Contents

Advertisement

INSTALLING THE POWER EXTEND CONVERTER INTO A
DISTRIBUTION POSITION

Important Safety Instructions

DANGER! Adhere to the "Important Safety Instructions" starting on page 5 and those listed in the power
system manual.
ALERT! Only install the power extend converter into a -48 VDC distribution position.
NOTE!
The power extend converter can be inserted or removed with power applied (hot swappable) as
long as the power extend converter is inserted/removed with the enable/disable switch in the disabled
Figure 12
position (see
WARNING! The power extend converter and front mounting bracket becomes very hot during power
extend converter operation at heavy load. Wear heat resistant gloves or allow the power extend
converter to cool down before removing.

Restrictions

Refer to the power extend converter instruction manual (UM565050) for wire sizing restrictions.
Refer to Table 4 for spacing and power restrictions. This table shows how many converters can be placed side
by side before skipping a single space at certain average power levels. These power levels pertain to the
average output power (busy hour average power) drawn by the load including any power loss in the cable. The
peak power available from each unit remains at 1000 watts regardless of spacing or location. Use the calculator
tool that can be obtained at
systems/esure-power-extend-converter-c4858-1000/#/downloads
spacing requirement of the Power Extend Converter based on the RRU type (or peak load), use application
(host power system), trunk and jumper cable size and length, minimum source voltage and minimum RRU
operating voltage.
NOTE!
When installing a power extend converter mounting bracket kit covered by these instructions
onto a stand-alone distribution cabinet installed in an outside plant enclosure, leave the front door off
the stand-alone distribution cabinet when complete with the installation.
Table 4:
Spacing and Power Restrictions: Spec. No. 545277 and 520276 Operating in a 40°C Ambient
Distribution
Row
No Spaces
Row 1 Only
ALERT! When circuit breaker(s) and Power Extend Converter(s) (Model C48/58-1000B, Spec. No.
1C48581000B) are deployed in the same enclosure, circuit breaker(s) can only be loaded to 70% of rated
value.
Vertiv
| eSure™ Power Extend Converter Mounting Bracket and Door Kit Installation Manual (IM60017372) | Rev. C
on page 21).
https://www.vertiv.com/en-us/products-catalog/critical-power/dc-power-
Watts Per Power Extend Converter
1 Pole / Space
375 W
900 W
to determine the necessity, quantity and
2 Pole / Space
3 Pole / Space
750 W
600 W
4 Pole / Space
500 W
16