Download Print this page

Johnson Controls York YIA Series Wiring Diagram page 9

Field control modifications

Advertisement

FIG. 14 – MULTIPLE UNITS (TWO) – PARALLEL
OPERATION – INDIVIDUAL UNIT PUMPS
(COOLING APPLICATION ONLY)
MULTIPLE UNITS (TWO) – PARALLEL
OPERATION – INDIVIDUAL UNIT PUMPS
This piping arrangement is the same as Fig. 15, ex‑
cept that the chilled water pumps associated with each
evaporator are cycled ON and OFF with the unit. This
results in reduced chilled water flow rates whenever
a single unit can handle the cooling load. Because no
chilled water flows through the inoperative unit, the
mixed water temperature peculiar to using a single pump
is avoided. When one unit is cut-out by the sequence
control (Fig. 12) the temperature of the supply chilled
water does not change.
JOHNSON CONTROLS
EVAPORATOR
EVAPORATOR
LD06829
EVAPORATOR
EVAPORATOR
FIG. 15 – MULTIPLE UNITS (TWO) – PARALLEL
OPERATION – SINGLE CHILLED WATER
PUMP (COOLING APPLICATION ONLY)
MULTIPLE UNITS (TWO) – PARALLEL OPERATION
– SINGLE CHILLED WATER PUMP
For this piping arrangement, each chiller's water sensor
is located in its own leaving water nozzle. This produces
a constant "mixed" chilled water temperature when
both units are operating. When either unit is cycled off
by the sequence control (Fig. 12), mixed chilled water
tempera ture will rise as a result of uncooled return water
flowing through the inoperative unit. For individual unit
chilled water pump piping, refer to Fig. 14.
FORM 155.21-W2 (1209)
LD06830
9

Advertisement

loading