ABB i-bus
®
KNX
Commissioning
Note
The physical address for the tunneling connection must fit the topology. Therefore, the addresses must
be selected from the address range of the subordinate line. On delivery, all tunneling servers have the
address 15.15.100.
In ETS 5, the first five free addresses in the line are assigned automatically after the Interface has been
inserted into a line.
The tunneling servers can also be encrypted with KNX Secure. When KNX Secure mode is activated,
a client will need the password assigned in ETS.
For details, see chapter 3.5,
3.4.1

Tunneling server settings

An additional Properties window is available in ETS for setting the additional physical addresses.
After insertion of the Interface into the line, ETS automatically reserves the first five free addresses of this
line for the tunneling servers of the Interface. This is a property of ETS and cannot be changed.
The addresses will be available in the device after the first download.
If this is not desired, the setting can be changed manually in the Properties window.
To change the address, mark the current device address or additional address and then select the desired
numerals using the up or down arrow key. The changed address is saved when another address is
marked.
The changed addresses are adopted by the device only after a download.
Park
If the option Park is activated for a tunnel, this tunnel will receive the address 15.15.255.
If the option Park is selected for all tunneling servers, all tunneling servers will be assigned the address
15.15.255. Only one tunneling server is available as a result.
KNX
Secure.
IPS/S 3.5.1 | 9AKK107680A8655 EN Rev. A 23