2.5
Configuring I/O
I/O MODULE DEFINITION FOR :
Slot
Slot Number
1
2
3
4
2-14
Installation
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
After you have inserted the module into the base, you must register the
module in PLC memory.
NOTE: If you do not register the module, the PLC logs a nonfatal error;
however, the module LED status indicator remains on.
Configure the analog modules as 8-point word as shown in Table 2-1.
Table 2-1 Module I/O Values
PPX:505–6108-A 8-channel analog input module
PPX:505–6208-A 8-channel analog output module
PPX:505–6108-B 8-channel analog input module
PPX:505–6208-B 8-channel analog output module
Figure 2-10 shows the typical screen used when configuring I/O (base 0,
modules installed in slots 1 and 2).
I/O Address
The module is logged in as
eight words (WX for inputs
and WY for outputs)
I/O
Number of Bit and Word I/O
Address
.....
0001
.....
.....
0009
.....
.....
0000
.....
.....
0000
.....
Figure 2-10 Sample I/O Module Definition Chart
For more information on configuring I/O, refer to your SIMATIC 500/505
TISOFT Release 6.3 User Manual.
Module
Base Number
Displays number
of the current base.
CHANNEL 1 BASE 00
X
Y
WX
WY
00
..
00
..
08
..
00
00
..
00
..
00
..
08
00
..
00
..
00
..
00
00
..
00
..
00
..
00
SF Module
The default for this definition is no.
Series 505 Analog I/O Modules User Manual
WX
WY
08
00
00
08
08
00
00
08
Special
Function
.......
No
.......
No
.......
No
.......
No