Table B-2 Analog Input Module PPX:505–6108A Electrical Specifications
Number of input points
Module width
Signal range
(selected voltage range applies to all channels)
Voltage accuracy
Current accuracy
Temperature coefficient
Voltage input
Current input
Repeatability
Resolution (input)
Analog-to-digital conversion
Conversion method
Input system conversion time delay
Update time
Sample repetition time
Input filter delay time
DC input resistance
Input protection
Voltage
Current
Type of protection
Module power from base
User power requirements
Input signal wiring
B-2
Specifications
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
8, single-ended
Single-wide
–5 V to +5 V and 0 to 20 mA, or
–10 V to +10 V
( ) 0.82% of full scale over operating range
( ) 0.5% of full scale at 25 C
( ) 1.25% of full scale over operating range
( ) 0.7% of full scale at 25 C
58 ppm/ C
83 ppm/ C
( ) 0.1% of full scale over operating range
12 bits plus sign, 1.25 mV or 5
12 bits plus sign
Dual slope integration
330 ms max
250 ms max (for all channels)
250 ms max
75 ms typical
Ω
1M
min with 5 V range selected
Ω
500k
min with 10 V range selected
Overvoltage to 30 VDC
Overcurrent to 30 mA
clamp diodes, optical isolation
4 W max, 2.5 W typical
None
Shielded, twisted-pair cable
(14–24 AWG or 0.18–1.5 mm
Series 505 Analog I/O Modules User Manual
µ
A ( 5 V range)
2
, stranded or solid)