THE PECO WAVE WIRELESS SYSTEM™

The PECO Wave Wireless System is comprised of the TW205 or TW206 wireless thermostat
paired with a RW205 receiver. Optional accessories to the system are the SW205 wireless
occupancy sensor and SW206 wireless door switch.
The TW205 thermostat is a nonprogrammable digital thermostat that may be powered by
battery, 24 VAC, or both. It features separate heating and cooling setpoints, auto changeover,
fan control functions, and wireless communication with the RW205 receiver. The RW205
receiver is wired to the HVAC equipment and controls all outputs. The optional SW205
occupancy sensor and SW206 door switch also communicate wirelessly with the RW205
receiver to signal occupancy status.
The TW206 thermostat is the programmable model. It includes all the features of the TW205
thermostat plus 7-day programming, four time periods per day, and hold/override options.

APPLICATIONS AND FEATURES

The PECO Wave Wireless System is intended for use in PTAC, PTHP, and On/Off control
applications.
• System mode selections include: Off-Heat-Cool-Auto-Setback
• Stages: 1 Heat/1 Cool, 2 Heat/1 Cool, 1 Heat/2 Cool
• 6 outputs (RW205): 1 Heat, 1 Cool, Up to 3 Fan, Outside Air Damper / Reversing Valve
• Fan control: 1-3 Speeds, Cycling (Auto) or Continuous (On)
• Permanent memory: The thermostat does not need batteries to store user-confi gured
settings in memory. Nonvolatile memory (EEPROM) saves temperature setpoints, fan, and
system settings for unlimited time. In the event of power loss, time settings are kept for at
least one year (TW206).
• Connections for Remote Temperature Probe and Setback (RW205)
RW205 REFERENCE
RW205 Front Cover
Device connection
indicator lights
Connect button
(use paperclip
tip to depress)
RW205 with Front Cover removed to
show terminals and voltage switch
Voltage selection switch
(up position is 24V,
down position is 110V)
Terminals
© COPYRIGHT 2009 PECO, INC. ALL RIGHTS RESERVED.
RW205 Back
2 3 4 5 6 7 8
1
RW205 WIRELESS RECEIVER
INSTALLATION INSTRUCTIONS
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO
INSTALL, OPERATE OR SERVICE THIS THERMOSTAT.
Failure to observe safety information and comply with instructions could result
in PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect power before
installing or servicing and use only wiring with insulation rated for full thermostat
operating voltage.
Before installing this control, the Voltage Selection Switch must be placed in the
correct position. See instructions.
To avoid potential fi re and/or explosion do not use in potentially fl ammable or
explosive atmospheres.
Retain these instructions for future reference. This product, when installed,
will be part of an engineered system whose specifi cations and performance
characteristics are not designed or controlled by PECO. You must review your
application and national and local codes to assure that your installation will be
functional and safe.
SPECIFICATIONS
Temperature Range:
Differential:
Input Power:
Wireless Type:
Wireless Range:
Operating Temperature:
Shipping Temperature:
Operating Humidity:
Physical Dimensions:
RW205 Output Ratings:
Mounting slot
VOLTAGE
24 VAC
120 VAC
Wiring passage
240 VAC
277 VAC
COMBINED LOAD CURRENT NOT TO EXCEED 20 AMPS
Mounting slot
WAVE WIRELESS SYSTEM MOUNTING CONSIDERATIONS
When selecting mounting locations for Wave Wireless System components, it is important
to consider the number and types of obstructions between components. The Wave Wireless
System will communicate through walls and other obstructions but they will reduce the
effective operating range of these devices. Mounting any device within a metal enclosure
may signifi cantly reduce its communicating range. The Wave Wireless System uses
Frequency Hopping technology to improve its resistance to wireless interference; however,
malfunctioning or improperly used wireless devices may interfere with the Wave Wireless
System. Take note of any other wireless devices in use near the Wave Wireless System
before installation or if communication errors occur frequently.
WARNING
!
50° to 90°F (10° to 32°C)
1°F (0.5°C)
TW205 / TW206 thermostat: Two AA alkaline
batteries or 24 VAC, 50/60 Hz
RW205 receiver: 24 VAC or 100-277 VAC, 50/60 Hz
902 to 928 MHz Band, FHSS
(Frequency Hopping Spread Spectrum)
100 ft minimum in open air
0° to 120°F (-17° to 48°C)
-20° to 130°F (-28° to 54°C)
5% to 95% RH, non-condensing
TW205 / TW206: 4.5"H x 5.75"W x 1.1"D
RW205: 4.8"H x 3.8"W x 1.3"D
RATINGS
RES
PILOT
AMPS
DUTY
FLA
LRA
NA
NA
NA
24 VA
5.8
34.8
6.0
125 VA
2.9
17.4
5.0
125 VA
2.4
14.4
4.2
125 VA
P/N 69566 3220-2240 REV 0 PAGE 1
HP
NA
1/4
1/4
1/4