5.2.3.6
Status Words Eleven to Eighteen (STW11–STW18)
Status Words 11 through 18 report the status of the I/O modules contained on
the logical bases, as shown in Figure 5-6. Each bit corresponds to one module in
the base. If the module is in proper working order or if there is no module in that
slot, the corresponding bit is 0. If the occupied slot contains a malfunctioning
module, the bit is 1. See the example shown in Figure 5-7.
The PLC reports an I/O mismatch — an installed module does not agree with
the I/O configuration — as a failed I/O module. The module has not actually
failed. You should re-enter the I/O configuration for the slot in question.
Figure 5-6 Format of Status Words Eleven to Eighteen
Hardware and Installation User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com
STARTUP / TROUBLESHOOTING
Bit Number (Status Words 11–18)
1
2
3
4
5
6
7
8
Slot
Slot
5
1
Slot
Slot
6
2
Slot
Slot
7
3
Slot
Slot
8
4
Logical Base B
Status Word
Logical Base B
11
Base
12
Base
13
Base
14
Base
15
Base
16
Base
17
Base
18
Base
(STW11–18)
5-12
9
10 11
12
13 14 15 16
Slot
Slot
5
1
Slot
Slot
6
2
Slot
Slot
7
3
Slot
Slot
8
4
Logical Base A
Logical Base A
1
Base
0
3
Base
2
5
Base
4
7
Base
6
9
Base
8
11
Base
10
13
Base
12
15
Base
14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic ti535

Table of Contents