INSTALLING THE BATTERY

The TI525/TI535 PLCs are shipped with a lithium battery already installed.
This battery has a minimum storage lifetime of three years and a minimum
backup lifetime of six months (0_to 60_C). Follow the steps listed below to
replace the battery.
3.5.1

Model TI525 Battery Installation

The TI525 is capable of preserving system memory for at least ten minutes after
the battery and power have been disconnected. Complete the battery
replacement within this period if you wish to save information.
1. Disable all user-supplied power to the base.
2. Remove the PLC from the base. Do not touch the components on the
printed circuit board or short any etch lines or pins as this may
disrupt system memory. Do not place the PLC on a conductive
surface.
3. Check the battery backup switch (DIP 2, switch 1). If it is off and you
wish to retain system memory, turn the switch on.
4. Remove the battery from the clip and disconnect the leads.
5. The new battery should be a 3.0 VDC UL Recognized lithium battery
(PPX:2587678–8005). Connect the red wire to the positive pole and
the black wire to the negative pole of the new battery. Then insert
the new battery into the battery holder.
6. Insert the PLC into the base, enable power, and verify that the BATT
GOOD LED comes on.
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
INSTALLATION
3-17
Hardware and Installation User Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic ti535

Table of Contents