Selecting Ladder Memory Protection — TI525 Models
Switch 4 on DIP 2 prevents modifications to the RLL program in ladder memory.
Your programming unit refers to this switch as a keylock.
Refer to Figure 3-6. Turn switch 4 ON to prohibit changes to the program. Turn
switch 4 OFF to permit program editing.
Figure 3-6 Switch Settings — TI525 L-Memory Protection
Turning the L-memory protect switch on does not prevent
forcing I/O, changing variable memory, or switching the PLC
from PROGRAM to RUN mode. These actions may be initiated
with a programming device connected to the PLC, or a special
function I/O module designed for this type of interface to the
PLC, e.g., a Network Interface Module.
The RLL can also be changed through a special function
module, even when the memory protection is enabled with the
keylock. Do not depend upon this switch to prevent personnel
from interrupting your process.