6.2 Default setting

The setting sub-menu include "General" and "Advanced" items.
General setting items descript as following table:
Items
Battery type
configure suitable charging curve
Set actual battery capacity
Battery capacity
to choose suitable maximum
To configure load power source
Work mode
priority, details as chapter 5.2
To ensure the best compatibility
AC source
AC input
To configure maximum AC input
current limit
current, details as chapter 2.4
Under voltage
alarm
under voltage alarm threshold
Under voltage
protection
voltage disconnect threshold
To activate power save function
Power save
To configure power saving
Date & Time
Descriptions
Select battery type to
charging current
with AC input source
To configure battery
To configure battery low
mode threshold
To set date and time
Energier Apollo User Manual
Selectable options
AGM, GEL, traction,
semi-traction, flooded, LFP,
lead-carbon
~
50
3000AH
Power backup,
Solar mode
Standard, Weak-grid,
Generator, Weak-generator
~
1A
32A
24V:20.0~32.0VDC
~
48V: 40.0
64.0VDC
24V:20.0~25.6VDC
~
48V: 40.0
51.2VDC
Enable, disable
~
0.5%
1% rated power
mm/dd/yyyy, hh:mm:ss
36
Default setting
AGM
50AH
Power backup
Standard
32A
Lead acid 21.6VDC
LFP:24.8VDC
Lead acid 43.2VDC
LFP:46.5VDC
Lead acid 21.0VDC
LFP:23.2VDC
Lead acid 42.0VDC
LFP:44.0VDC
Disable
0.5%