4.7 Power Save mode (PS mode)

Using DIP Switch 7, you can set the system in power save mode. Please refer to chapter 2.12 for explanation.
4.8 Weak Grid and GEN mode
Through DIP Switch 1 and 8, you could configure the system to different modes for different appliance. For explanation, please refer
to chapter 2.11.
Dip switch 1
Off
Off
On
On
This configuration will adjust the minimum quality of AC input which Energier pro Inverter Charger Combination will
qualify and pass through to your AC appliance. Voltage or frequency variation might cause damage for particular load.
Before adjusting these setting, refer to electrical rating of connected load. Failure to follow the instruction can cause
damage over appliance connected.

4.9 AC input current setting

Through RCF supplied, you can set the AC input current. This configuration can be done only after Energier pro Inverter Charger Combination
was switched on.
Please refer to chapter 7.2 for detail instruction.
Dip switch 8
Mode
Off
Standard
On
GEN
Off
Weak Grid
On
GEN & Weak Grid
Voltage range
Frequency range
184 VAC-264 VAC
45 Hz-65 Hz
173 VAC-276 VAC
40 Hz-70 Hz
167 VAC-264 VAC
45 Hz-65 Hz
167 VAC-276 VAC
40 Hz-70 Hz
28
Energier pro User Manual
Waveform
sensitive
less sensitive
sensitive
less sensitive