General Advice; Fix Energier Apollo; Connection Of Battery Cables - TBB Energier Apollo CH2.0M User Manual

All in one inverter
Table of Contents

Advertisement

4.1.3 General advice

Ensure that Energier Apollo has the correct DC voltage with your existing battery system.
Install Energier Apollo as close to the batteries as possible reducing the voltage drop on cable for
the better performance of the equipment.
Do not connect the output of this equipment to your AC system at the same time as
any other AC source such as the 230V external mains or a generator.
On the AC output side, we recommend connecting the output from Energier Apollo to a suitable
Residual Current Device (RCD) and circuit breaker.
The neutral of this equipment cannot be connected to the earth. Otherwise the
equipment will be burned or user will get electric shocked in case of reversed
connection on L and N wire.

4.2 Fix Energier Apollo

Energier Apollo can be installed either vertically on wall or horizontally on floor. Please follow the
below procedure for wall mounting.

4.3 Connection of battery cables

Please make sure Energier Apollo turned off before connection. Otherwise, high
voltage can be present.
In order to fully utilize the full capacity of the product, batteries with sufficient capacity and battery
cables with sufficient cross section should be used. See table below.
Model No.
Recommended battery capacity (AH)
Recommended DC fuse
Maximum torque of battery terminals
Preassembled cable length 1.5m
1.5m - 5m
5m -10m
CH2.0M
CH2.0S
100AH-700AH
100AH-600AH
150A
12Nm
12Nm
Recommended cross section
25mm
2
16mm
35mm
25mm
2
70mm
50mm
2
17
Energier Apollo User Manual
CH3.0S
100AH-600AH
100A
120A
12Nm
2
16mm
25mm
2
50mm
2
CH4.0S
100AH-700AH
150A
12Nm
2
25mm
2
35mm
2
2
70mm
2
2