6. Installation and Connection

For the user operation safety, cut off the power before installation.

6.1 General advice

Ensure that the Energier pro Inverter Charger Combination has the correct DC voltage with your existing battery system.
Install Energier pro Inverter Charger Combination as close to the batteries as possible reducing the voltage drop on cable
for the better performance of the equipment.
Do not connect the output of this equipment to your AC system at the same time as any other AC source
such as the 230V external mains or a generator.
We recommend connecting a DC fuse corresponding to the conductor between battery and Energier pro Inverter Charger
Combination,which will offer protection to the battery cable. Please refer to following chart of our recommendations.
Systemcapacity
CF08xx
CF12xx
CF16xx
CF20xx
CF30xx
CF40xx
CF50xx
CF60xx
CF80xx
On the AC output side, we recommend connecting the output from Energier pro Inverter Charger Combination to a suitable
Residual Current Circuit Breaker and Circuit Breaker.
The neutral of this equipment is not connected to the earth. If requested, additional devices need to be installed internally.
Please contact your installer.
12 VDC model
150 A
200 A
250 A
300 A
500 A
/
/
/
/
30
24 VDC model
75 A
100 A
125 A
150 A
250 A
325 A
400 A
/
/
Energier pro User Manual
48 VDC model
/
/
/
80 A
125 A
175 A
200 A
250 A
300 A