Permissible Range Of Curvepoints - Siemens RVW26.000B27 Basic Documentation

Electronic air / fuel ratio control system
Table of Contents

Advertisement

Legend
Siemens Building Technologies
HVAC Products
Example:
1.
Set the maximum burner output (100 %) with an O
The positions are: «Air_Pos» = 9.40 and «FuelPos» = 8.32 .
2.
Reduce burner output to 93.7 % using the AZW....
For the moment, set «Air_Pos» = 9.40 and «FuelPos» = 8.32 for this load point.
3.
Reduce «FuelPos» until the O
setpoint of 2.00 % in the table). The O
4.
Reduce «Air_Pos» until the O
«Air_Pos» = 8.92.
5.
Reduce burner output to 87.5 % using the AZW...
For the moment, set «Air_Pos» = 8.92 and «FuelPos» = 7.92 for this load point.
6.
Reduce «FuelPos» until the O
reached at «FuelPos» = 7.18.
7.
Reduce «Air_Pos» until the O
cess air shall be higher. This is the case at «Air_Pos» = 8.40. With the next setting,
the column with the O
8.
Set the load points until the minimum output is reached, following the same proce-
dure.
9.
The curvepoints below the minimum output should be interpolated and then set.

18.2 Permissible range of curvepoints

Z
End switch position «Fully closed»
A
End switch position «Fully open»
T
End switch tolerance ±200 mV
Disturb
Impact of correcting variable
MinLoad / IgnitLo
Minimum load / ignition load
Load
Output signal with no correcting variable
MaxLoad
Maximum burner output
9,6
A
Disturb x MinLoad
Z
0,4
0
MinLoad
IgnitLo
Fig. 30
Permissible range of curvepoints
Electronic Air / Fuel Ratio Control System
18 Notes on the commissioning of a burner
value of 3.18 % is reached (column with the O
2
setpoint is reached at «FuelPos» = 7.92.
2
value of 2 % is reached. This is the case at
2
value of 3.26 % is reached. The O
2
value of 2.2 % is reached because the level of ex-
2
setpoint of 2.20 % applies.
2
100 %
Load [%]
value of 2 %.
2
2
MaxLoad
CC1P7873.1en
15.10.2002
2
value is
T
T
100
63/69