Siemens RVW26.000B27 Basic Documentation page 62

Electronic air / fuel ratio control system
Table of Contents

Advertisement

Creating the
auxiliary table
Legend
62/69
Siemens Building Technologies
HVAC Products
B. Curve adjustment by O
curvepoints, see below)
(less accurate, but quicker)
Procedure (e.g. highlighted table column)
1.
Determine the amount of fuel at maximum burner output and set it. Set the fan
speed to the required O
2.
Set the RVW25... and the RVW26... to the next lower loadpoint (93.7 %) while
maintaining the positions for fuel and air. Here, warning «-58 / Monoton fail») will
be delivered. Ignore this message when making the next settings.
3.
Reduce the amount of fuel until the O
load point (93.7 %) is reached.
4.
Reduce the air volume until the demanded O
ther the O
value of the table column used until now (2.2 %) or the value of another
2
column (e.g. 2.40 %). Warning «-58») must now disappear within 20 to 30 sec-
onds.
5.
Repeat steps 2 through 4 until the minimum burner output is reached.
6.
Interpolate the curvepoints below the low-fire position values (e.g. 0 %).
O
setpoint [%]
4.00
2
Number (l)
1.24
Output (P) [%]
100
4.00
93.75
5.06
87.50
5.13
81.25
5.21
75.00
5.30
68.75
5.41
62.50
5.54
56.25
5.69
50.00
5.88
43.75
6.11
37.50
6.41
31.25
6.82
25.00
7.38
18.75
8.23
12.50
9.63
Procedure:
1.
Consider the admissible range of curvepoints
2.
Calculate the O
table values:
2
Pnew
O
new = 20.9 % -
2
Pold
3.
Calculate the air number (l):
20.9 %
l
=
(20.9 % - O
setpoint)
2
O
setpoint
O
table value of the load (P = 100 %)
2
2
O
new
O
value after fuel reduction
2
2
Pnew
Required load value after fuel reduction
Pold
Current load value before fuel reduction
Electronic Air / Fuel Ratio Control System
18 Notes on the commissioning of a burner
value with the help of an auxiliary table (e.g. for 17
2
setpoint (e.g. 2.20 %).
2
value (3.37 %) listed in the table for this
2
3.80
3.60
3.40
3.20
1.22
1.21
1.19
1.18
3.80
3.60
3.40
3.20
4.87
4.68
4.49
4.31
4.94
4.75
4.57
4.38
5.02
4.84
4.65
4.46
5.12
4.93
4.75
4.56
5.23
5.04
4.86
4.68
5.35
5.17
4.99
4.81
5.51
5.33
5.15
4.97
5.70
5.52
5.34
5.17
5.94
5.76
5.59
5.41
6.24
6.07
5.90
5.73
6.65
6.48
6.32
6.15
7.22
7.06
6.90
6.74
8.08
7.93
7.78
7.63
9.50
9.37
9.23
9.10
x (20.9 % - O
setpoint)
2
setpoint is reached. This can be ei-
2
3.00
2.80
2.60
2.40
1.17
1.15
1.14
1.13
3.00
2.80
2.60
2.40
4.12
3.93
3.74
3.56
4.19
4.01
3.82
3.63
4.28
4.09
3.91
3.72
4.38
4.19
4.01
3.82
4.49
4.31
4.13
3.94
4.63
4.45
4.26
4.08
4.79
4.61
4.43
4.25
4.99
4.81
4.63
4.46
5.24
5.06
4.89
4.71
5.56
5.39
5.21
5.04
5.98
5.82
5.65
5.48
6.58
6.42
6.26
6.10
7.48
7.33
7.18
7.03
8.97
8.83
8.70
8.57
2.20
2.00
1.12
1.11
2.20
2.00
3.37
3.18
3.46
3.26
3.54
3.35
3.64
3.45
3.76
3.58
3.90
3.72
4.07
3.89
4.28
4.10
4.54
4.36
4.87
4.70
5.32
5.15
5.94
5.78
6.87
6.73
8.43
8.30