Siemens RVW26.000B27 Basic Documentation page 16

Electronic air / fuel ratio control system
Table of Contents

Advertisement

Control of the
actuator positions
16/69
Siemens Building Technologies
HVAC Products
For each actuator and each type of fuel, the RVW26... allows load / position curves to
be programmed (refer to chapter «Programming»).
This means that a total of 4 curves can be programmed on the RVW26...
AUX1(1)
Curve for auxiliary actuator «SA5» with fuel 1
AUX1(2)
Curve for auxiliary actuator «SA5» or «SA6» with fuel 2
AUX2(1)
Curve for auxiliary actuator «SA7» with fuel 1
AUX2(2)
Curve for auxiliary actuator «SA7» with fuel 2
Auxiliary actuator «AUX2» can be deactivated via a parameter. For every output,
burner output «Load» is assigned a position via its curve. According to the fuel selec-
tion made at «F1» or «F2», a maximum of 2 curves is thus selected (also refer to sec-
tion «Selection of fuel»).
X1
0...10 V
U1
Integrator
0...10 V
Load
Fig. 10
Load settings
Setload
Output as defined by the integrator (internal signal) with a value of be-
tween 0...100 %
Load
Current burner output as predefined by the RVW25... with a value of be-
tween 0...100 %
Position
Position of the actuators with a value of between DC 0.4...9.6 V
The load / position curves can be programmed across the entire burner output range
(0...100 %).
On the RVW25..., 2 load limits can be set, separately for each type of fuel:
·
«MinLoad» is the burner's minimum ouptut (low-fire)
·
«MaxLoad» is the burner's maximum output (high-fire)
During normal burner operation, the current «Load» is available at terminal «X1» as a
DC 0...10 V signal.
Electronic Air / Fuel Ratio Control System
5 Description of functions
Setload
Fuel
select
F1
F2
AUX1(1)
Position
Position
Load
AUX1(2)
Position
Position
Load
AUX2(1)
Position
Position
Load
AUX2(2)
Position
Position
Load
78731c02/0601
CC1P7873.1en
15.10.2002