Description Of The Inputs / Outputs - Siemens RVW26.000B27 Basic Documentation

Electronic air / fuel ratio control system
Table of Contents

Advertisement

Terminal
Input / output
B2
I
B3
I
B4
I
F1
I
F2
I
L
I
N
I
M
Q1
O
Q2
I
Q3
I
Q4 – Q5 / H
O
TxD
O
RxD
I
GND
U1
I
U3
I
U10
O
X1
O
X2
I
X3
O
Y3
O
Y4
O
Y5
O
Y6
O
Y8
O
Y10
I
Y20
I
+5 V
O
32/69
Siemens Building Technologies
HVAC Products

9.2 Description of the inputs / outputs

Voltage
DC 0...10 V
Potentiometer (wiper ) from auxiliary actuator (AUX1(1))
DC 0...10 V
Potentiometer (wiper) from auxiliary actuator (AUX1(2))
DC 0...10 V
Potentiometer (wiper) from auxiliary actuator (AUX2)
AC 230 V
Fuel selection: Fel 1
AC 230 V
Fuel selection: Fuel 2
AC 230 V
Live for internal power supply, actuator outputs and «Q1»
Neutral conductor for internal power supply, reference potential for the mains
voltage inputs (all N-terminal are internally interconnected)
Reference potential for all low voltage inputs / outputs and for the screening
(all M-terminals are internally interconnected)
AC 230 V
Acknowledge signal: Indicates to the burner control when certain actuator posi-
tions are reached
AC 230 V
Signal from burner control: First fuel valve on / off
AC 230 V
Signal from burner control: Fan on / off
potential free Readiness contact / control loop: Indicates operational readiness of the
RVW26...
Interface for the RVW25.000B27
Interface for the RVW25.000B27
Reference potential for the interface
DC 0...10 V
Signal input for analog burner output control
DC 0...10 V
Signal input for predefined speed from the RVW25...
DC 10 V
Power supply for potentiometers (all «U10» terminals are internally intercon-
nected)
DC 0...10 V
Burner load signal
DC 0...10 V
Correcting variable signal from O
DC 0...10 V
Predefined speed for the variable speed drive
AC 230 V
Positioning signal (open) for actuator «AUX1»
AC 230 V
Positioning signal (close) for actuator «AUX1»
AC 230 V
Positioning signal (open) for actuator «AUX2»
AC 230 V
Positioning signal (close) for actuator «AUX2»
AC 230 V
Positioning signal for the RVW25..: valve «ON / OFF»
AC 230 V
Signal for prepurging from the burner control
AC 230 V
Signal for ignition position and «CLOSE» position from the burner control
DC 5 V
Auxiliary voltage, max. 1 mA
Electronic Air / Fuel Ratio Control System
9 Assignment of terminals and description of inputs / outputs (I / O)
Description
trim control of the RPO25...
2
CC1P7873.1en
15.10.2002