General - Siemens SINAMICS G130 Operating Instructions Manual

Line reactors
Hide thumbs Also See for SINAMICS G130:

Advertisement

General

Description
Line reactors limit low-frequency line-side harmonics to permissible values.
Non-observance of the fundamental safety instructions and residual risks
The non-observance of the fundamental safety instructions and residual risks stated in
Chapter 1 can result in accidents with severe injuries or death.
• Adhere to the fundamental safety instructions.
• When assessing the risk, take into account residual risks.
Burns resulting from high surface temperature
The line reactors can become very hot. You can get seriously burnt when touching the
surface.
• Mount the line reactors so that contact is not possible. If this is not possible, attach
• To prevent adjacent components from suffering damage due to these high
NOTICE
Damage of the system caused by the use of inappropriate and not approved line reactors
Inappropriate and not approved line reactors can damage the Line Modules.
Line harmonics that damage/disturb other loads connected to the same line supply can also
occur.
• Only use line reactors listed in this manual.
Note
Malfunctions through magnetic fields
Reactors produce magnetic fields that can disturb or damage components and cables.
• Arrange the components and cables at a suitable distance (at least 200 mm) or shield the
magnetic fields appropriately.
Line reactors
Operating Instructions, 11/2017, A5E00331462A
WARNING
CAUTION
clearly visible and understandable warning notices at hazardous positions.
temperatures, maintain a clearance of 100 mm on all sides of the line reactors.
2
11