Electrical installation

Connection
When connecting the line filter and line reactor, you must take into account the following
conditions to ensure that they function correctly:
● Use shielded control cables. The shield must be connected at both ends.
● With analog control cables, connecting the shield at both ends can result in coupled-in
noise. To prevent this, the shield must only be connected at one end on the Power
Module.
● Control cables must be routed separately from power cables. Power cables are motor
cables or connecting cables from the DC link of the Power Module (terminals
DCPA/DCNA) to other components (e.g. Braking Module). In particular, you must ensure
that control cables and power cables are not routed in parallel in a joint cable raceway,
even if all the cables are shielded.
● You must use shielded motor cables. The shield for the motor cable must be attached to
the shield plate and motor housing.
● The ground wire for the motor must be fed directly back to the Power Module.
Connection overview
Figure 4-1
Line reactors
Operating Instructions, 11/2017, A5E00331462A
Connecting the line filter, line reactor, and Power Module