Technical Data - Vents VUT 550 PBW EC User Manual

Heat and energy recovery air handling unit
Table of Contents

Advertisement

TECHNICAL DATA

The unit is designed for application with the ambient temperature ranging from +1 °C to +40 °C and relative humidity up to 80 %.
In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 2-3 °C above
the dew point temperature of the transported air.
The unit is rated as a Class I electrical appliance.
Hazardous parts access and water ingress protection rating:
IP22 for the unit connected to the air ducts
IP44 for the unit motors
The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.
Supply voltage, 50 (60) Hz [V]
Maximum fan power [W]
Number of water heater rows
Maximum unit current [A]
Maximum air flow [m
/h]
3
RPM [min
]
-1
Sound pressure level at 3 m distance [dBA]
Transported air temperature [°С]
Casing material
Insulation, mineral wool [mm]
Filtering class of the extract filter
Filtering class of the supply filter
Connected air duct diameter [mm]
Weight [kg]
Heat recovery efficiency [%]
Heat exchanger type
Heat exchanger material
SEC class
*The VUE units are equipped with an enthalpy heat exchanger and do not require condensate drainage.
ø d
6
MODEL
L
L1
TECHNICAL DATA
VUT/VUE 550 PBW EC
3100
78...90/69...87
VUT/VUE 550 PBW EC
VUT/VUE 900 PBW EC
1~ 230
297
2
2,4
620
30
-25...+40
Aluzinc
20
G4
G4 (optionally – F7)
200
68
Counter-flow
Polystyrene/Enthalpy
A
www.ventilation-system.com
VUT/VUE 550/900 PBW EC
442
4
3
1030
2720
33
250
112
75...88/69...85
A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vue 550 pbw ecVut 900 pbw ecVue 900 pbw ec