Mounting And Set-Up - Vents VUT 550 PBW EC User Manual

Heat and energy recovery air handling unit
Table of Contents

Advertisement

VUT/VUE 550/900 PBW EC

MOUNTING AND SET-UP

While mounting the unit provide enough space for its maintenance or repair work.
A – minimum required access distance for water heater installation.
The distance is selected depending on the installation conditions at the discretion of the installer.
The unit must be suspended to the ceiling on the threaded rod that is fixed inside a dowel.
Example
Nut
Washer
Vibration-absorbing
rubber
Nut and
lock-nut
To attain the best performance of the unit and to minimise turbulence-induced air pressure losses, connect a straight air duct section on
both sides of the unit while mounting.
Minimum straight air duct length:
equal to 1 air duct diameter on the intake side
equal to 3 air duct diameters on the outlet side
If the air ducts are too short or not connected, protect the unit parts from ingress of foreign objects, e.g. by covering the spigots with a
protecting grille or other protecting device with mesh width not more than 12.5 mm to prevent uncontrollable access to the fans.
www.ventilation-system.com
MINIMUM DISTANCE FOR ACCESSING THE UNIT
min 20 mm
min B
A
Model
VUT/VUE 550 PBW EC
min B, mm
UNIT INSTALLATION
READ THE USER'S MANUAL BEFORE INSTALLING THE UNIT.
VUT/VUE 900 PBW EC
850
800
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vue 550 pbw ecVut 900 pbw ecVue 900 pbw ec

Table of Contents