KEYSTONE OM13 - EPI-2 3-WIRES MODULE
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Alternatively, to avoid induced voltage phenomena over floating command line, the following wiring diagram may be used.
Monitor
Switch
(Note 1)
NOTES
1. Supply from 110 to 240 V AC / 1-ph
L2 neutral
When L1 - L2 - L3 cables are long (more than
10 metres) induced voltage phenomena may occur
on floating command line.
To avoid this unwanted effect, realize a cabling
system where unused line (either L1 OPEN or
L3 CLOSE) is pulled to NEUTRAL line. To do this a
switch may be used.
USE TO AVOID INDUCED VOLTAGE PHENOMENA
Blinker/
CLC1
Local selector
relay
relay
(Note 3)
For example with the BACO PN NC02GQ1 the
following configuration may be used:
short circuit
short circuit
short circuit
short circuit
pin 3 = PHASE
pin 5 = NEUTRAL (L2)
pin 2 = OPEN (L1)
pin 4 = CLOSE (L3)
CLC2
OPC1
OPC2
Output contacts
(Note 2-4)
MODULE 13 (3-WIRES)
pins 1 and 3
pins 5 and 7
pins 2 and 8
pins 4 and 6
2. Contacts shown in intermediate position
CLC1 - CLC2 end of travel signaling in CLOSING
Contacts shown in intermediate position
OPC1 - OPC2 end of travel signaling in OPENING
3. Internal heater (max. 10 watt) is activated when a
power supply from 110 to 240 V AC is connected to
the terminals 33-34
4. Output contact rating: 240 V AC / 5 A - 30 V DC /
5 A - 120 V DC / 0.5 A
11