Figure 2.4 Digitrip Neutral Sensor Types
L
N
B-7
2
B-6
R/1
Notes:
In this scheme, all breaker secondary currents (at the 100 mA level) are summed together at the PC
1
board donut transformer to sense ground fault via element R
2
Do not jumper on secondary contacts B-6, B-7. This will defeat all ground fault protection in
application for 4 pole breaker.
3
Ground fault style trip unit is installed.
Figure 2.5 4-Pole–3200A Frame Using Residual Ground Fault (Earth-Fault) Sensing