22
Appendix 3 Parameter Setting Table
Sensor Calibration
Display Setting
Humidifier Run Hours
Run Hours
Heater1 Run Hours
Heater2 Run Hours
Airflow Detect
CW Setting
EC Fan Control
Monitor Setting
Shutdown Mode
Password Setup
Parameter Reset
Fan Run Hours
Comp1 Run Hours
Comp2 Run Hours
PACC11Z Precision Air Conditioner User Manual
Detect Mode
DT
DT Alarm Setpoint
15℃
CW Run Mode
Rotation
CW Default
A
CW Rotation Time
0min
CW Detection Time
5min
CW Loss Temp
15℃
CW/Comp Shift DT
4℃
2Port Valve Flush
Dis
Fan Ctrl Mode
Auto
Fanspeed STD
100%
Fanspeed MIN
90%
ESP Setpoint
25Pa
ESP Control Period
30s
ESP Sensor Quantity
0
ESP Sensor1 Weight
50%
ESP Sensor2 Weight
50%
Return Temp
0℃
Calibrated
Return Hum Calibrated
0℃
Protocol
YDN23
Monitor ID
1
Baud Rate
9600
Monitor Shutdown
En
Level 1 PSW
0001
Level 2 PSW
Parameter Backup
No
Restore Backup
No
Restore Default
No
Display Group
0
Display Address
0
Display Contrast
50%
Run Hours Threshold
30000h
HRS Exceeded Reset
No
Run Hours Threshold
30000h
HRS Exceeded Reset
No
Run Hours Threshold
30000h
HRS Exceeded Reset
No
Run Hours Threshold
30000h
HRS Exceeded Reset
No
Run Hours Threshold
30000h
HRS Exceeded Reset
No
Run Hours Threshold
30000h
HRS Exceeded Reset
No
DT/DP
5℃~30℃
Both/Rotation
A/B
0min~30000min
2min~10min
12℃~20℃
2℃~20℃
Dis/En
Auto/Manual/ESP
0%~100%
0%~100%
0Pa~300Pa
10s~100s
0/1/2
0%~100%
0%~100%
-10℃~10℃
-20℃~20℃
YDN23/Modbus
1~254
1200/2400/4800/9600/19200
Dis/En
0000~9999
0000~9999
No/Yes
No/Yes
No/Yes
0~1
0~31
0%~99%
0h~30000h
No/Yes
0h~30000h
No/Yes
0h~30000h
No/Yes
0h~30000h
No/Yes
0h~30000h
No/Yes
0h~30000h
No/Yes

Advertisement