Emerson Liebert PEX+ Series User Manual page 23

Precision air conditioner controller
Hide thumbs Also See for Liebert PEX+ Series:
Table of Contents

Advertisement

Hum Control
Input Setup
Config Menu
System
Config
Delay Setting
PACC11Z Precision Air Conditioner User Manual
Sample Time
25s
I Parameter
90s
D Parameter
5s
Proportional Max
100%
Integral Max
100%
Differential Max
100%
PID Change Max
20%
Fill Rate
150%
Prefill Time
60/30s(IFL/IFM)
Run Interval
15h
Hum Time
10/8min(IFL/IFM)
50/30min(IFL/IFM
Fill Time
)
Flush Time
10s
Hum Ctrl Type
Rel
Hum DeadBand
0%RH
Disable Hum When Heat
Yes
Dehum Low Limit
-3℃
General Alarm
NO
Remote Shutdown
NC
Analog Input1
Amp
Analog Input2
Amp
Analog Input3
Vol
Analog Input4
Vol
Smoke Input
NO
Heater Input
NC
Customer Input1
NO
Customer Input2
NO
Comp Cool Type
Air
Comp Quantity
2
CW Source
0
Heater Quantity
1
Humidifier Type
IFL
LP Sensor Type
Analog
Fan Start Delay
10s
Fan Stop Delay
30s
LP Delay Time
180s
Comp Min ON Time
360s
Comp Min OFF Time
180s
Comp Swap Mode
No
Comp Swap Interval
100h
Comp Start Interval
3s
LLBP Pre-time
2s
LLBP Post-time
10s
Appendix 3 Parameter Setting Table
1s~300s
0s~9000s
0s~9000s
0%~200%
0%~200%
0%~200%
0%~200%
100%~500%
10s~300s
5h~25h
1min~30min
1min~900min
5s~30s
Rel/Abs
0℃~10℃
No/Yes
-10℃~0℃
NO/NC
NO/NC
Amp/Vol
Amp/Vol
Amp/Vol
Amp/Vol
NO/NC
NO/NC
NO/NC
NO/NC
Air/Water
0/1/2
0/1/2
0/1/2
None/IFM/IFL/OEM
Switch/Analog
10S~600s
10S~300s
30S~600s
60S~600s
60S~600s
No/Yes
100h~1000h
1s~30s
0s~30s
0s~30s
21

Advertisement

Table of Contents
loading

Table of Contents