Appendix 3 Parameter Setting Table
Temp/Hum Setting
System Status
Input Status
System
Setting
Coil1 Frost
Coil2 Frost
Filter Maintenance
Humidifier Fail
Humidifier High Water
Stat Pres Sensor Fail
Temp/Hum Board Fail
Smoke Detected Alarm
Heater Alarm
Customer Input1
Customer Input2
Water Underfloor
NTC1 Fail
NTC2 Fail
NTC3 Fail
Unit Addr Overlap
Loss Of Slave Unit
Loss Of Master Unit
Fan HRS Exceeded
Hum HRS Exceeded
Comp1 HRS Exceeded
Comp2 HRS Exceeded
Heater1 HRS Exceeded
Heater2 HRS Exceeded
High Return Temp
Low Return Temp
High Return Hum
Low Return Hum
Alarm Setting
High Supply Temp
Frost Low Pressure
Discharge High Temp
Discharge Low Temp
Return Temp Setpoint
Supply Temp Setpoint
Return Temp Band
Return Hum Setpoint
Return Hum Band
NTC0 Temp
Temp Calirated
Supply Air/Coil Temp
Temp Calirated
CW/Discharge1 Temp
Temp Calirated
CW/Discharge2 Temp
Temp Calirated
Temp DeadBand
Temp Control
Temp Ctrl Type
Control Mode
PACC11Z Precision Air Conditioner User Manual
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En
En
Msg/En
En
Msg/En
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
En
Msg/En/Dis
30℃
20℃~35℃
15℃
5℃~20℃
80%RH
65%RH~90%RH
20%RH
10%RH~35%RH
23℃
13℃~35℃
4.3Bar
3.5Bar~7.0Bar
120℃
100℃~150℃
60℃
30℃~90℃
24℃
18℃~32℃
18℃
8℃~30℃
4℃
1℃~10℃
50%RH
20%RH~80%RH
5%RH
1%RH~10%RH
0℃
-10℃~10℃
0℃
-10℃~10℃
0℃
-10℃~10℃
0℃
-10℃~10℃
0℃
0℃~5℃
Proportion
Proportion/PID
Return
Return/Supply