Installation Guide
English – September 2015
Introduction
This installation guide provides instructions for
installation, startup and adjustment. To receive a copy
of the instruction manual, contact your local Sales
Office or view a copy at www.fisherregulators.com.
For further information refer to: Type LR125 Instruction
Manual, D103576X012.
P.E.D. Categories
This product may be used as a safety accessory
with pressure equipment in the following Pressure
Equipment Directive 97/23/EC categories.
PRODUCT SIZE
DN 25 and 50 / 1 and 2 in.
DN 80 and 100 / 3 and 4 in.
Specifications
Main Valve Body Sizes, End Connection Styles
and Structural Design Ratings
See Table 1
Outlet (Control) Pressure Ranges
See Table 3
Main Valve Minimum Differential Pressure
See Table 6
Maximum Inlet Pressure
Type LR125 Main Valve: See Table 1
Type MR95H/MR95HP Pilot: See Table 2
Type 112 Restrictor: 103 bar / 1500 psig
Temperature Capabilities
See Table 4
Main Valve Internal Inlet Strainer Sizes
DN 25 / 1 in.:
12 Mesh (1.68 mm / 0.0661 in.)
DN 50, 80 and 100 / 2, 3 and 4 in.:
10 Mesh (2 mm / 0.0787 in.)
Installation
!
Only qualified personnel shall install or
service a regulator. Regulators should
be installed, operated and maintained
in accordance with international and
applicable codes and regulations and
Fisher
instructions.
®
1. The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.
2. Nominal sieve opening.
CATEGORY
FLUID TYPE
SEP
Liquid
II
Liquid
(1)
(1)
(1)
(1)
(2)
(2)
WARNING
www.fisherregulators.com
If the regulator vents fluid or a
leak develops in the system, it
indicates that service is required.
Failure to take the regulator out of
service immediately may create a
hazardous condition.
Personal injury, equipment damage
or leakage due to escaping fluid
or bursting of pressure containing
parts may result if this regulator is
overpressured or is installed where
service conditions could exceed the
limits given in the Specifications
section or where conditions exceed
any ratings of the adjacent piping or
piping connections.
To avoid such injury or damage,
provide pressure-relieving or
pressure-limiting devices (as required
by the appropriate code, regulation
or standard) to prevent service
conditions from exceeding limits.
Additionally, physical damage to the
regulator could result in personal
injury and property damage due to
escaping fluid. To avoid such injury
and damage, install the regulator in a
safe location.
Clean out all pipelines before installation of the
regulator and check to be sure the regulator has
not been damaged or has collected foreign material
during shipping. For NPT bodies, apply pipe
compound to the external pipe threads. For flanged
bodies, use suitable line gaskets and approved
piping and bolting practices. Install the regulator in
any position desired, unless otherwise specified,
but be sure flow through the body is in the direction
indicated by the arrow on the body.
It is important that the regulator be
installed so that the vent hole in the
spring case is unobstructed at all
times. For outdoor installations, the
regulator should be located away
from vehicular traffic and positioned
so that water, ice and other foreign
materials cannot enter the spring
case through the vent. Avoid placing
the regulator beneath eaves or
downspouts and be sure it is above
the probable snow level.
Type LR125
Note

Advertisement

loading

Summary of Contents for Emerson Fisher LR125 Series

  • Page 1 Installation Guide Type LR125 English – September 2015 Introduction If the regulator vents fluid or a leak develops in the system, it This installation guide provides instructions for indicates that service is required. installation, startup and adjustment. To receive a copy Failure to take the regulator out of of the instruction manual, contact your local Sales service immediately may create a...
  • Page 2 Type LR125 Table 1. Type LR125 Main Valve Body Sizes, End Connection Styles, Structural Design Ratings and Maximum Operating Inlet Pressure STRUCTURAL DESIGN MAXIMUM OPERATING MAIN VALVE BODY SIZE MAIN VALVE BODY RATING INLET PRESSURE END CONNECTION STYLES MATERIAL psig psig NPT or SWE (1 and 2 in.
  • Page 3: Overpressure Protection

    Type LR125 Table 5. Main Valve Maximum Pressure Ratings, Diaphragm Selection Information and Main Spring Selection MAXIMUM OPERATING MAXIMUM OPERATING MAXIMUM EMERGENCY INLET BODY SIZE DIAPHRAGM INLET PRESSURE DIFFERENTIAL PRESSURE AND DIFFERENTIAL PRESSURE (3)(4) MAIN SPRING COLOR MATERIAL psig psig bar d psid 17E68 Nitrile (NBR)
  • Page 4: Parts List

    Type LR125 49B6019_A 48B2142_C DN 25 / 1 IN. BODY SIZE DN 50, 80 AND 100 / 2, 3 AND 4 IN. BODY SIZES APPLY LUBRICANT / SEALANT L1 = LITHIUM POLYMER TYPE LUBRICANT (MULTI-PURPOSE GREASE) L2 = ANTI-SEIZE LUBRICANT S = MEDIUM STRENGTH THREADLOCKER 1.
  • Page 5 Type LR125 GF04914 APPLY LUBRICANT / SEALANT L1 = GENERAL PURPOSE PTFE OR LITHIUM GREASE L2 = ANTI-SEIZE COMPOUND 1. Lubricant and sealant must be selected such that they meet the temperature requirements. 2. Apply L2 (anti-seize compound) on key 16 for Stainless steel bolts. Figure 2.
  • Page 6 For further information visit www.fisherregulators.com The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC, a business of Emerson Process Management.