Volvo Penta TWD1643GE Series Operator's Manual page 28

Hide thumbs Also See for TWD1643GE Series:
Table of Contents

Advertisement

Instruments and Controls
26
Customer parameter / Gen set
Primary engine speed - selection of engine rpm,
1500 or 1800 rpm.
Preheat on ignition - activation of automatic pre-
heating. The engine control system senses if pre-
heating is needed and activates it directly at switch-
on.
Governor droop (%) - setting of droop level, when
activated. For activation, refer to "Governor droop"
in the main menu.
Overspeed limit (%) - setting of limit for overspeed
alarm, % of set engine rpm.
Overspeed shutdown - activation of engine shut-
down with overspeed alarm. Refer to "Overspeed
limit" to activate the alarm limit for the excess rpm
alarm.
Oil temp warning limit (°C) - setting alarm limit for
oil temperature.
Coolant temp limit (°C) - setting alarm limit for
coolant temperature.
Throttle input setting
rpm control setting (throttle operation).
Set throttle mode - OFF - engine rpm is controlled
via the DCU panel.
ext throttle input - engine speed is controlled with a
potentiometer (accelerator).
ext voltage input - engine rpm is controlled by an
external unit.
Set idle voltage (V) - idle voltage level setting.
Set max voltage (V) - full throttle voltage level
setting.
47711296 01-2019 © AB VOLVO PENTA