Contents Contents General information........................ 4 About this documentation .................... 4 Underlying standards ...................... 4 Structure of the safety notes ................... 4 Rights to claim under limited warranty ................ 5 Content of the documentation.................. 6 Exclusion of liability...................... 6 Other applicable documentation .................. 6 Product names and trademarks.................. 6 Copyright notice ...................... 6 Integrated safety technology....................
General information About this documentation General information About this documentation This documentation is an integral part of the product. The documentation is written for all employees who assemble, install, start up, and service this product. Make sure this documentation is accessible and legible. Ensure that persons respons- ible for the machinery and its operation as well as persons who work on the product independently have read through the documentation carefully and understood it.
General information Rights to claim under limited warranty This is the formal structure of a safety note for a specific section: SIGNAL WORD Type and source of hazard. Possible consequence(s) if disregarded. • Measure(s) to prevent the hazard. Meaning of the hazard symbols The hazard symbols in the safety notes have the following meaning: Hazard symbol Meaning...
General information Content of the documentation Content of the documentation The current version of the documentation is the original. This document contains additional safety-relevant information and conditions for use in safety-related applications. Exclusion of liability Read the information in this documentation, otherwise safe operation is impossible. You must comply with the information contained in this documentation to achieve the specified product characteristics and performance features.
Integrated safety technology Safe condition Integrated safety technology ® The safety technology of MOVIGEAR described below has been developed and tested in accordance with the following safety requirements: • SIL 3 according to EN 61800-5-2:2007 • PL e according to EN ISO 13849-1:2008 This was certified by TÜV Nord.
Page 8
Integrated safety technology Safety concept ® 2.2.1 Schematic representation "Safety concept for MOVIGEAR " The following figure shows a schematic representation of the safety concept for ® MOVIGEAR Safety µC 2463070859 Safety controller/safety relay external Connection "STO+" Connection "STO-" Motor phase Motor ®...
Integrated safety technology Safety functions Safety functions The following drive-related safety functions can be used: 2.3.1 • STO (safe torque off according to EN 61800-5-2) by disconnecting the STO input. If the STO function is activated, the frequency inverter no longer supplies power to the motor for generating torque.
Page 10
Integrated safety technology Safety functions 2.3.2 SS1(c) • SS1(c) (safe stop 1, function variant c according to IEC 61800-5-2) by means of suitable external control (e.g. safety relay with delayed disconnection) The following sequence is mandatory: – Decelerate the drive using an appropriate brake ramp specified via setpoints. –...
Integrated safety technology Limitations Limitations WARNING The safety concept is only suitable for performing mechanical work on driven sys- tem/machine components. When the STO signal is disconnected, the line voltage is still present at the DC link ® of the MOVIGEAR drive unit.
Safety conditions Safety conditions ® The requirement for safe operation is that the safety functions of MOVIGEAR properly integrated into an application-specific higher-level safety function. A system/ machine-specific risk assessment must be carried out through the system/machine manufacturer and taken into account for the use of the drive system with ®...
Safety conditions Approved units Approved units ® Only the following unit variants of MOVIGEAR B are permitted for safety-related ap- plications. Type code DSM- SNI- example Description Product Gear Shaft Housing Size Motor Installation Ver- family unit type mounting type technology sion tions...
Safety conditions Installation requirements Installation requirements • Power lines and STO control lines have to be routed in separate cables. This does not apply to cables approved by SEW‑EURODRIVE specifically for this case of ap- plication. ® • The line length between the safety controller and MOVIGEAR may not exceed 100 m.
Page 15
Safety conditions Installation requirements ® MOVIGEAR DBC-B and DAC-B Remove the jumpers between STO input (terminals 1/2) and 24 V output (ter- minals 6/7): 9007202406743947 ® MOVIGEAR DSC-B and SNI-B Remove the jumpers between STO input (terminals 1/2) and 24 V output (ter- minals 5/15): 9007202406745867 ®...
Safety conditions Requirements on external safety controllers and safety relays Requirements on external safety controllers and safety relays A safety relay can be used as an alternative to a safety controller. The following re- quirements apply analogously. • The safety controller and all other safety-related subsystems must be approved and tested for at least that safety class which is required in the overall system for the respective, application-related safety function.
Page 17
Safety conditions Requirements on external safety controllers and safety relays – When connected, the switch-off test pulses may not be longer than 1 ms. The next pulse blanking cannot reoccur earlier than after 20 ms. High: no STO <1 ms >20 ms Low: STO active 9007201720642187 3.3.1...
Safety conditions Startup requirements Startup requirements • To validate the implemented safety functions, they must be documented and checked after successful startup (validation). Observe the limitations for safety functions in chapter "Limitations" for the valida- tion of the safety functions. Non-safety-relevant parts and components that affect the result of the validation test must be deactivated, if necessary.
Technical data Technical data ® The table below shows the technical data for MOVIGEAR relating to the integrated ® safety technology. The technical data and approvals in the respective MOVIGEAR operating instructions must be observed in addition. Technical data of the STO input Min.
Appendix Unit variants with DynaStop Appendix Unit variants with DynaStop ® Unit variants with DynaStop WARNING ® The electrodynamic deceleration function DynaStop does not allow for a definite stop at a position. Severe or fatal injuries. • Do not use the electrodynamic deceleration function for hoists. ®...
Page 21
Appendix Unit variants with DynaStop ® The following figure shows the use of the DynaStop function in connection with the STO function: Deceleration ramp Speed Drive enable signal Control signal active DynaStop ® inactive 9007201718955403 Parameter setting "8584.0 – Brake function": 1 = ON (All variants) Factory setting of parameter "8584.0 –...
Page 22
Appendix Unit variants with DynaStop 5.1.2 Behavior when STO is activated before standstill NOTICE ® Depending on the setting in parameter "9833.20", the DynaStop function can be ac- tivated outside the permitted operating range. This can cause a high torque load/high motor currents, which may damage the drive unit and the application.
Page 23
Appendix Unit variants with DynaStop Factory setting/recommended settings The following figure shows the behavior when STO is activated before the motor is at standstill in connection with the following parameter setting: Parameter "9833.20 – Activation of DynaStop® for STO": 0 = NO (Factory setting/recommended settings): Speed Deceleration...
Appendix Connection variants Connection variants 5.2.1 Position of the terminals for safe torque off (STO) The following figure shows an example of the terminal positions at MGF..-DSC-B for ® safe torque off (STO) of MOVIGEAR 11 12 2552708747 5.2.2 Assignment of the terminals for safe torque off (STO) The following figure shows the terminal assignment for safe torque off (STO) of ®...
Page 25
Appendix Connection variants 5.2.3 Position of the optional plug connectors for safe torque off (STO) The following figure shows an example of the position of the STO plug connectors X5502 "STO" and X5503 "STO". The plug connectors are always in "position 3". Plug connector Color Posi-...
Page 26
Appendix Connection variants 5.2.4 Assignment of the optional plug connectors for safe torque off (STO) X5502: STO WARNING ® No safe disconnection of the MOVIGEAR drive unit. Severe or fatal injuries. • Do not use the 24 V output (pins 1 and 3) for safety-related applications with ®...
Page 27
Appendix Connection variants Connection cable INFORMATION Use only shielded cables for this connection and only appropriate plug connectors that connect the shield with the unit in an HF-compatible manner. The following table shows the cables available for this connection: Connection cable Conformity/ Cable type Length/in-...
Page 28
Appendix Connection variants Connection cable Conformity/ Cable type Length/in- Cable cross part number stallation section/op- type erating voltage LEONI Variable 2 × ® 18127401 BETAflam – 0.75 mm 145C-flex DC 60 V M12, 5-pin, A- M12, 5-pin, A- CE/UL: HELU- Variable ® coded, coded, 18147704...
Page 29
Appendix Connection variants Connection of cables with open end The following table shows the conductor assignment of cables with the following part numbers: • 18124976 • 18147690 • 18164390 • 18127398 • 18153445 • 18164315 Signal name Core color/designation STO − Black/1 STO + Black/2...
Page 30
Appendix Connection variants X5503: STO The following table shows information about this connection: Function Connection for safe disconnection (STO) Connection type M12, 5-pin, male, A-coded Wiring diagram Assignment Name Function Res. Reserved STO − STO − connection Res. Reserved STO + STO + connection Res.
Page 31
Appendix Connection variants Connection cable INFORMATION Use only shielded cables for this connection and only appropriate plug connectors that connect the shield with the unit in an HF-compatible manner. The following table shows the cables available for this connection: Connection cable Conformity/ Cable type Length/in-...
Appendix Connection of an external safety relay for STO Connection of an external safety relay for STO 5.3.1 Connection via terminals The following figure shows a connection example with a safety relay and disconnec- tion of all poles: DC +24 V 1 STO + IN 2 STO ̶...
Page 33
Appendix Connection of an external safety relay for STO 5.3.3 Connection via terminals – group disconnection The following figure shows a connection example for disconnection of group drives with a safety relay: DC +24 V 1 STO + IN 2 STO ̶ 11 STO + OUT 12 STO ̶...
Page 34
Appendix Connection of an external safety relay for STO 5.3.4 Connection via M12 plug connectors – group disconnection The following figure shows a connection example for disconnection of group drives with a safety relay: DC +24 V X5502 X5503 X5502 X5503 9007201723394443 ®...
Page 35
Appendix Connection of an external safety relay for STO 5.3.5 STO signal for group disconnection Requirements ® For group drives, the STO signal for several MOVIGEAR drives can be provided by a single safety relay. The following requirements must be met: •...
Appendix Connection of an external safety controller for STO Connection of an external safety controller for STO 5.4.1 Connection via terminals The following figure shows a connection example with a safety controller and discon- nection of all poles for STO: DOn_P 1 STO + IN 2 STO ̶...
Page 37
Appendix Connection of an external safety controller for STO 5.4.3 Connection via terminals – group disconnection The following figure shows a connection example for disconnection of group drives with a safety controller: DOn_P 1 STO + IN 2 STO ̶ DOn_M 11 STO + OUT 12 STO ̶...
Page 38
Appendix Connection of an external safety controller for STO 5.4.4 Connection via M12 plug connectors – group disconnection The following figure shows a connection example for disconnection of group drives with a safety controller: X5502 DOn_P DOn_M X5503 X5502 X5503 9007202062818699 ®...
Page 39
Appendix Connection of an external safety controller for STO 5.4.5 STO signal for group disconnection Requirements ® For group drives, the STO signal for several MOVIGEAR drives can be provided by a single safety controller. The following requirements must be met: •...