3.5 Installation notes

◆Please place the UPS in a clean, stable environment, avoid the vibration, dust, humidity,
flammable gas and liquid, corrosive objects. To avoid from high room temperature, a system of
room extractor fans is recommended to be installed. Optional air filters are available if the UPS
operates in a dusty environment.
◆The environment temperature around the UPS should keep in a range of 0℃~40℃. If the
environment temperature exceeds 40℃, the rated load capacity should be reduced by 12% per
5℃. The max temperature can't be higher than 50℃.
◆If the UPS is dismantled under low temperature, it might be in a condensing condition.The
UPS can't be installed unless the internal and external of the equipment is fully dry. Otherwise,
there will be in danger of electric shock.
◆Batteries should be mounted in an environment where the temperature is within the required
specs. Temperature is a major factor in determining battery life and capacity. In a normal
installation, the battery temperature is maintained between 15° C and 25° C. Keep batteries away
from heat sources or main air ventilation area, etc.
WARNING!
Typical battery performance data are quoted for an operating temperature between
20° C and 25° C. Operating it above this range will reduce the battery life while
operation below this range will reduce the battery capacity
◆ Should the equipment not be installed immediately it must be stored in a room so as to
protect it against excessive humidity and or heat sources 。
CAUTION!
An unused battery must be recharged every 6months. Temporarily connecting the
UPS to a suitable AC supply and activating it for the time required for recharging
the batteries are required.
◆The highest altitude that UPS may work normally with full load is 1500 meters. The load
capacity should be reduced when this UPS is installed in place whose altitude is higher than
1500 meters, shown as the following table:
(Load coefficient equals max load in high altitude place divided by nominal power of the UPS)
Altitude(m)
Load coefficient
◆To get the UPS completely monitored by the software, you just simply connect RS232
cable to each end of the computer and the UPS respectively.

External Protective Devices

3.6
For safety reasons, it is necessary to install, external circuit breaker at the input A.C. supply
and the battery. This chapter provides guidelines for qualified installers that must have the
knowledge of local wiring practices for the equipment to be installed.
External Battery
The UPS and its associated batteries are protected against the effect of over-current
through a DC compatible thermo-magnetic circuit-breaker (or a set of fuses) located
close to the battery.
UPS Output
Any external distribution board used for load distribution shall be fitted with protective
devices that may avoid the risk of UPS overloaded.
1500
2000
2500
100%
95%
90%
3000
3500
85%
80%
6
.
4000
4500
5000
75%
70%
65%