Feature 07 – Floor Temp Limit: This function is available when mode 06 is set to 03 or 04.
You can set a oor limiting temperature between 20-45°C (28°C is the default setting).
Note: Air Sensor only MUST NOT be used to control electric under- oor heating.
Floor Sensor or Both should be used.
Feature 08 – Optimum Start: Optimum start will delay the start up of the heating
system to the latest possible moment to avoid unnecessary heating and ensure the
building is warm at the programmed time. The thermostat uses the rate of change
information to calculate how long the heating needs to raise the building temperature
1°C (with a rate of change of 20, the thermostat has calculated the heating needs 20
minutes to raise the building temperature 1°C) and starts the heating accordingly.
Feature 09 – Rate of Change: Number of minutes for 1°C temperature rise.
Feature 10 – Not used on this model.
Feature 11 – Not used on this model.
Feature 12 – Program Mode: Non-Programmable, Weekday/Weekend (5/2),
7 Day Programming or 24 Hour. The thermostat o ers three programming modes and the
option of con guring it to work as a non-programmable thermostat.
Weekday/ Weekend - allows you to program 4 comfort levels for the weekday and
4 di erent comfort levels for the weekend.
7 Day Program Mode - Each day has 4 comfort levels that can be programmed
independently.
24 Hour Mode - All days are programmed the same and repeat continuously.
Feature 13 - Temperature Format: This function allows you to select between °C and °F.