Delta CliQ DRP024V060W1AA Technical Data Sheet page 3

Din rail power supply
Table of Contents

Advertisement

TECHNICAL DATASHEET
CliQ DIN Rail Power Supply
24V 60W 1 Phase / DRP024V060W1AA
Mechanical
Case Cover / Chassis
Dimensions (L x W x D)
Unit Weight
Indicator
Cooling System
Terminal
Wire
Mounting Rail
Noise (1 Meter from power supply)
Environment
Surrounding Air Temperature
Power De-rating
Operating Humidity
Operating Altitude
Shock Test
Vibration
Over Voltage Category
Pollution Degree
Protections
Overvoltage
Overload / Overcurrent
Over Temperature
Short Circuit
Internal Fuse at L pin
Protection Against Shock
*PE: Primary Earth
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
3
www.DeltaPSU.com (November 2020, Rev. 08)
Aluminium
121 x 32 x 120 mm (4.76 x 1.26 x 4.72 inch)
0.37 kg (0.82 lb)
Green LED
DC OK
Convection
Input
3 Pins (Rated 300V/20A)
Output
2 Pins (Rated 300V/20A)
Input / Output
AWG 20-14
Standard TS35 DIN Rail in accordance with EN 60715
Sound Pressure Level (SPL) < 40dBA
Operating
-20°C to +80°C
Storage
-25°C to +85°C
< 0°C de-rate power by 1% / °C,
Vertical Mounting
> 50°C de-rate power by 2.5% / °C
< 0°C de-rate power by 1% / °C,
Horizontal Mounting
> 50°C de-rate power by 2.5% / °C
> 70°C de-rate power by 4% / °C
5 to 95% RH (Non-Condensing)
0 to 2,000 Meters (6,560 ft)
Non-Operating
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,
3 times per direction, 18 times in total
Non-Operating
IEC 60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak);
90 min per axis for all X, Y, Z direction
III
2
32V ±10%, SELV Output, Hiccup Mode,
Non-Latching (Auto-Recovery)
> 150% of rated load current, Hiccup Mode,
Non-Latching (Auto-Recovery)
< 80°C Surrounding Air Temperature @ 100% load,
Non-Latching (Auto-Recovery)
Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
T3.15AH
Class I with PE* connection
According to IEC/EN 62477-1
(clearance and creepage distances)

Advertisement

Table of Contents
loading