Honeywell NX series User Manual page 114

Constant and variable torque variable speed drives for induction motors
Hide thumbs Also See for NX series:
Table of Contents

Advertisement

Actual value special display
The Actual value special display parameters are used to convert and display the actual value signal
in a form more informative to the user.
The Actual value special display parameters are available in PID Control Application and Pump and
Fan Control Application:
Par ID
Parameter name
ID1033
Actual value special display minimum
ID1034
Actual value special display maximum
ID1035
Actual value special display decimals
ID1036
Actual value special display unit
Example:
The actual value signal sent from a sensor (in mA) represents the amount of waste water pumped
from a tank per second. The signal range is 0(4)...20mA. Instead of receiving the level of the actual
value signal (in mA) on the display, you wish to receive the amount of water pumped in m
then set a value for par. ID1033 to correspond to the minimum signal level (0/4 mA) and another
value for par. ID1034 to correspond to the maximum signal level (20 mA). The number of decimals
needed can be set with par. ID1035 and the unit (m
value signal is then scaled between the set min and max values and displayed in the selected unit.
The following units can be selected (par. ID1036):
Value
Unit
0
Not Used
1
2
3
4
5
mbar
6
7
8
9
m / s
10
11
l / min
12
13
m3 /s
14
m3 /min
NOTE: The maximum number of characters that can be shown on keypad is 4. This means that in
some cases the display of the unit on the keypad does not comply with the standards.
On keypad
%
%
°C
°C
m
m
bar
bar
mbar
Pa
Pa
kPa
kPa
PSI
PSI
m/s
l / s
l/s
l/m
l / h
l/h
m3/s
m3/m
Parameter code in
PID ctrl applic.
2.2.46
2.2.47
2.2.48
2.2.49
3
/s) with par. ID1036. The level of the actual
Value
Unit
15
m3 /h
°F
16
17
ft
18
gal / s
gal / min
19
20
gal / h
21
ft3 / s
22
ft3 / min
23
ft3 / h
24
A
25
V
26
W
27
kW
28
Hp
Parameter code in
Pump&Fan ctrl applic.
2.9.29
2.9.30
2.9.31
2.9.32
3
/s. You
On keypad
m3/h
°F
ft
GPS
GPM
GPH
CFS
CFM
CFH
A
V
W
kW
Hp

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents