EMS 5000 FIREPOINT

8. Main Panel Step By Step Software configuration

Note: it is assumed that all installation procedures are complete.
Firstly, at the master panel, insert the Key into the Panel's Control Keyswitch, located at
the right of the Panel. Turn the Key to the "ON" Position.
Step
No
1
Press the "0" key followed by the "" button until the
screen displays:
2
Press the "YES" key and the screen will now display:
3
Press the "" button until the screen displays:
4
Press the "YES" key and the screen will
now display:
5
Enter 221100 then press the "YES" key and the screen
will now display:
6
Press the "" button until the screen displays:
7
Press the "YES" key followed "0" key on
the Keypad the screen will now display:
8
Press the "" button until the screen displays:
9
Press the "YES" key. The screen will now display:
©2015 EMS Security Group Ltd. All rights reserved.
Action
8
Screen Display
| Logging
>Fire System Opts <
| Remote Access
Yes = select
Time
| ** Fire system ** |
>Dev. Disable/Test<
| Net. Disable/Test |
Yes= Select
Time
| System Mode
>Engineers Config <
| Printer Options
Yes= Select
Time
Enter Your PIN
For Access>
Then Press YES
Time
| ** Eng. Config **
> Device Database <
|
Sounder Options |
Yes= Select
Time
| Reset Security
> Reset System
| Lan Options
Yes= Select
Time
|** Main Menu **
> Pins & Access <
|
System Support |
Yes= Select
Time
| System Support
> Serial Comms
| Pager Setup
Yes= Select
Time
|*
Serial Comms *|
> Device Table
| Re-start bus
Yes= Select
Time
TSD233 Iss 3 25/06/15 AJM
|
|
|
|
|
|
<
|
|
|
<
|
<
|