EMS 5000 FIREPOINT

5. Factory Supplied Pre-Programmed Systems

For a factory set pre-programmed system, there will only be a few steps necessary to
online the network path.
Necessary connections made as shown in diagram number PO4334.
Once the connections have been made, power should be applied to the slave panels
followed by the master panel.
On powering up the master panel, the system should automatically go online.
With all the Control Panels powered the master panel will automatically try to re-online
the pre-programmed slave panels. This can take up to 5 minutes to complete. With
control panels offline an 'OL' fault will be displayed at the master panel. This fault will
automatically clear when all panels are online.

6. Should a slave panel go offline

The following type of fault screen should be displayed:
At the master panel, turn the control key switch to the "ON" position.
Press the "0" key and scroll down to "Engineers Config".
Press the "YES" key, enter 221100 then press the "YES" key.
Scroll down to "Reset System" and press the "YES" key followed by the "0" key.
Scroll down to "Serial Comms" and press the "YES" key.
Scroll down to "Re-start bus and press the "YES" key.
The bus will be re-started and the screen will display the following when finished:-
©2015 EMS Security Group Ltd. All rights reserved.
01 FAULT
TOT
01
Control Panel
Offline
Node : 03 ON H/W BUS
Re-initialising Bus
Please wait....*Done*
Push any key
TIME
6
TSD233 Iss 3 25/06/15 AJM