Installation Wiring
2.7.10 LCD-SLP Installation Wiring Diagram
Figure 2.7.10.1 illustrates the LCD-SLP circuit board diagram. For system assembly and installation wiring
terminal designations, refer to the LCD-SLP Installation Instructions, P/N: LS10045-000GF-E. You can
download this document from the Gamewell-FCI Website (www.gamewell-fci.com).
2.7.11 LCD-SLP Installation Wiring Terminals
Table 2.7.11.1 lists the LCD-SLP installation wiring designations.
Designation
TB1-1
TB1-2
TB1-3
TB1-4
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
J5
J6
W1
SW1
NOTE 1: If you do not use J5, these connections are required.
NOTE 2: Use this connection only in remote installations. Do not use this connection when the
LCD-SLP is mounted in the same cabinet with the SLP-E3.
22
TB4
TB3
TB2
REMOTE
SLP-E3
ANNUNCIATORS
W1
J7
Figure 2.7.10.1 LCD-SLP Circuit Board Diagram
Description
RS-485A
Communications IN (See Notes 1 & 2)
RS-485B
Communications IN (See Notes 1 & 2)
RS-485A
Communications OUT (See Note 2)
RS-485B
Communications OUT (See Note 2)
+24 V
+24 V non-resettable power IN (See Notes 1 & 2)
GND IN
GROUND IN (See Notes 1 & 2)
+24 V OUT
+24 V non-resettable power OUT (See Note 2)
GND OUT
GROUND OUT (See Note 2)
GND
Extra Ground
Earth Ground
Earth Ground
Local Connection
RS-485 communications and power (ribbon cable local only)
(See Note 3).
Keypad Lock
Jumper or Keyswitch:
1. To use the Jumper, do either of the following:
JMP IN
JMP OUT = Enabled
OR
2. To use the keyswitch, connect the PK-625 keyswitch.
This keyswitch is keyed alike with the door lock, and must be
operated to activate the keypad.
RS-485 Termination
W1 should be ON (top 2 pins), if it is the first or last device on the
RS-485 bus. Otherwise, W1 should be OFF (bottom 2 pins).
Display Address
Binary Switch Addressing (See Note 4)
Table 2.7.11.1 LCD-SLP Installation Wiring Terminals
S3 Series UL Listing Document — P/N LS10005-051GF-E:D3 3/09/2016
Remote Annunciator/Keypad Circuits
TB1
B- B+
SLC-PM/SLC95-PM #1
J5
J1
SLC-PM/SLC95-PM #2
J6 J1
BAR CODE
LABEL
PRODUCT
SERIAL NUMBER
PRODUCT
DATE CODE
LABEL
Comments
= Disabled
NOTES
TB5
J2
ETHERNET