10.1 Requirements

The sound pressure level of the surroundings in which an audible alarm device is to be installed must be
measured.
The sound pressure level of the alarm device must be at least 65 dB and must be +10 dB higher at all
locations than the sound pressure level that was measured for the surroundings. If necessary, several alarm
devices may have to be planned.
The sound pressure level of the signal tone (e.g. DIN tone) that is also going to be used later for alarm
output in these surroundings, must also be measured.
The signal tone must be clearly audible above the background noise. In case of similar frequencies, a
different signal tone must be chosen and/or the alarm must be signalled with an additional optical alarm
device.
In accordance with DIN 33404-3, an alarm signal and/or signal template for alarms (e.g. comprising
signal tone + voice output) must always begin with the DIN tone. Then a voice message may be
output.
If possible, the audible alarm devices should be configured in control zones with a low control zone number.
Low control zone numbers are activated quicker than high control zone numbers. Relay/LED outputs should
have higher control zone numbers than alarm devices. As many loop activations as possible should be
assigned to a control zone.
Synchronisation is carried out at all esserbus
The gap between the synchronisation signals must be coordinated with the signal templates that were
aggregated in the tools 8000 programming software (e.g. consisting of signal tone + voice output).
If an alarm device is replaced with the device, all the activations are transferred. If an alarm device is
replaced by a device from another zone, all activations are deleted, including the activations in the sectors.

10.2 Project planning information

10.2.1 IQ8Quad with integrated alarm devices
The sound pressure levels for IQ8Quad with integrated alarm devices and IQ8Alarm Plus in accordance with
EN 54-3 are set out in the following tables.
Tone
Description
Alternating signal tone,
Frequency 800 Hz/970 Hz @ 2 Hz
2
(based on FP 1063.1 Telecoms BS
5839 Pt1-Tone 1)
Continuous signal tone,
7
Frequency 970 Hz
(based on BS 5839 Pt1)
Alternating signal tone,
Frequency 1200 ... 500 Hz @ 1 Hz,
10
DIN tone in accordance with DIN 33404-
3 (factory setting)
Alternating signal tone,
11
Frequency 554 Hz @/440 Hz
(based on French fire sound)
Rising signal tone,
12
Frequency 500 Hz ... 1200 Hz
(based on NL - Slow Whoop)
Continuous signal tone,
13
Frequency 485 Hz
(based on US Horn)
Cyclic signal tone,
14
Frequency 485 Hz (based on US Horn
with Temporal Pattern)
TI 798960.GB0 / 04.20
Periphery components for ESSER FACP
®
PLus modules that are operated on a FACP.
Sound pressure level (SPL) [dB(A)]
Horizontal angle [°]
15
45
75
105
135
81
84
84
84
83
83
85
87
88
85
84
84
88
88
83
81
84
87
89
84
86
86
88
87
85
77
74
80
82
77
75
72
78
82
77
Vertical angle [°]
165
15
45
75
105
81
84
83
85
85
82
86
86
88
89
83
84
84
86
87
80
81
84
85
86
84
85
86
87
87
76
79
75
82
82
73
78
75
82
82
135
165
83
85
86
85
83
82
83
80
85
84
78
78
78
81
65