SLP-E3 Main Circuit Installation Wiring Diagram

2.2 SLP-E3 Main Circuit Installation Wiring Diagram
The S3 Series System uses the SLP-E3 main board as the main circuit board. Figure 2.2.1 shows the SLP-E3
main circuit board sub-assembly.
FORM "C" DRY
CONTACTS
RS-485 BUS
INTERFACE
AUXILIARY POWER
MUNICIPAL/
RELEASING CIRCUIT
NON-POWER-LIMITED/
POLARITY REVERSAL
POWER-LIMITED
2.2.1 SLP-E3 Main Circuit Board Installation Wiring Terminals
Table 2.2.1.1 lists the SLP-E3 main board installation wiring terminals.
Designation
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB3-1
TB3-2
TB3-3
TB3-4
TB4-1
TB4-2
TB4-3
TB4-4
Table 2.2.1.1 SLP-E3 Main Circuit Board Installation Wiring Terminals
S3 Series UL Listing Document — P/N LS10005-051GF-E:D3 3/09/2016
SW3
SW2
SW5
SW4
TB4
TB3
SLP-E3
TB2
W1
CLASS 2
J7
J1
TB6
Figure 2.2.1 SLP-E3 Main Circuit Board
Description
NAC 1 B+
Notification Appliance Circuit 1, B+
NAC 1 B-
Notification Appliance Circuit,1 B-
NAC 1 A+/NAC 3 B+ Notification Appliance Circuit 1, Class A+ RETURN or Notification
Appliance Circuit 3 B+
NAC 1 A-/NAC 3 B- Notification Appliance Circuit 1, Class A- RETURN or Notification
Appliance Circuit 3 B-
NAC 2 B+
Notification Appliance Circuit 2 B+
NAC 2 B-
Notification Appliance Circuit 2 B-
NAC 2 A+/NAC 4 B+ Notification Appliance Circuit 2 Class A RETURN A+ or Notification
Appliance Circuit 4 B+
NAC 2 A-/NAC 4 B- Notification Appliance Circuit 2 Class A RETURN A- or Notification
Appliance Circuit 4 B-
RESET B+
Resettable 24 VDC Auxiliary Power
GND
Resettable or Non-Resettable Power Common Negative
AUX B+
Non-resettable 24 VDC Auxiliary Power
Make no connection
MUNI +
Positive Output to Local Energy City Box, Remote Station or Releasing
Solenoid (See Note 1 and Jumper W1).
MUNI -
Negative Output to Local Energy City Box, Remote Station or Releasing
Solenoid (See Note 1 and Jumper W1).
RS-485 Interface
AUX RS-485 COMM A Output
RS-485 Interface
AUX RS-485 COMM B Output
Ground
Earth Ground
Reserved
Spare (N/C)
ALRM NC
Alarm relay contact normally CLOSED N/C
ALRM NO
Alarm relay contact normally OPEN N/O
ALRM C
Alarm relay contact common
SUPV NC
Supervisory relay contact normally CLOSED N/C
NAC CIRCUITS
TB1
SLC-PM/SLC95-PM #1
B- B+
J5
J1
SLC-PM/SLC95-PM #2
J6 J1
NETWORK
J4
W3
J3
JTAG
PRODUCT
DATE CODE
LABEL
BAT+ BAT-
Comments
Installation Wiring
SLC
CIRCUITS
FOR SYSTEM
(SEE WARNING).
SENSOR
TB1
(SLC-PM)
OR
APOLLO
(SLC95-PM)
DEVICES.
(SEE WARNING).
(SEE NOTE 1)
TB1
NOTE 1:
DO NOT
COMBINE
SLC-PM WITH
SLC95-PM.
- IF SYSTEM
SENSOR, USE
TB5
SLC-PM.
- IF APOLLO,
USE SLC95-PM.
BAR CODE
LABEL
PRODUCT
SERIAL NUMBER
WARNING!
INSTALLTHE
SLC-PM/
SLC95-PM
COMPONENT
SIDE UP!
SW1
J2
ETHERNET
11