Precautions When Doing Riser Piping Work - Gree GMV-ND100L/A-T Service Manual

Multi variable air conditioners indoor units
Hide thumbs Also See for GMV-ND100L/A-T:
Table of Contents

Advertisement

GREE
When unifying multiple drain pipes, install the pipes as shown below. Select converging drain
pipes whose gauge is suitable for the operating capacity of the unit (take the cassette type unit
for example).

4.3 Precautions when doing riser piping work

Make sure that heat insulation work is executed on the following 2 spots to prevent any possible
water leakage due to dew condensation.
a)
Connect the drain hose to the drain raiser pipe, and insulate them.
b)
Connect the drain hose to the drain outlet on the indoor unit, and tighten it with the clamp
(take the cassette type unit for example).
Secure a downward gradient of 1/100 or more for the drain pipe. To accomplish this, mount
supporting brackets at an interval of 1 - 1.5 m (take the cassette type unit for example).
GMV5 INDOOR UNIT SERVICE MANUAL
129