Piping Work - Gree GCAT24F/NaA Owner's Manual

Table of Contents

Advertisement

A-Coil
When installing in an area directly over a finished ceiling (such as an attic), an
emergency drain pan is required directly under the unit. See local and state codes for
requirements. When installing this unit in an area that may become wet, elevate the unit
with a sturdy, non-porous material. In installations that may lead to physical damage (i.e.
a garage) it is advised to install a protective barrier to prevent such damage.
It is necessary to allow a minimum of 40" between the inlet/outlet of the indoor unit
and wall, as shown below.

4.3 Piping Work

4.3.1 Specification of Connection Pipe
Model
GCAT24F/NaA
GCAT36F/NaA
GCAT48H/NaA
GCAT60H/NaA
4.3.2 Piping Preparation
4.3.2.1 Solder Connection
All cut ends are to be round, burr free, and cleaned. Failure to follow this practice
increases the chances for refrigerant leakage.
External diameter (inch)
Gas pipe
Φ3/4
6
Liquid pipe
Φ3/8