Gree GMV-ND100L/A-T Service Manual page 76

Multi variable air conditioners indoor units
Hide thumbs Also See for GMV-ND100L/A-T:
Table of Contents

Advertisement

GREE
Parameter
Parameter Name
Code
Environment
temperature
P20
sensor settings
for IDU
Corrected value
of environment
temperature
P21
sensor of IDU
(for cooling,
dehumidifying,
and air supply)
Corrected value
of environment
temperature
P22
sensor of IDU
(for heating, fast
heating, and air
warming)
Capacity
P32
adjustment
function of IDU
Factory setting
P35
recovery for user
functions
Factory setting
recovery for
P36
engineering
settings
Prevention for
P40
heat collection
Parameter Range
01: temperature sensor
of air return vent
02: temperature sensor
of wired controller
03: temperature sensor
of air return vent for
cooling, dehumidifying,
and air supply;
temperature sensor of
wired controller for
heating
04: temperature sensor
of wired controller for
cooling, dehumidifying,
and air supply;
temperature sensor of
air return vent for
heating
-15 to +15
-15 to +15
-40% to +40%
00: invalid
01: valid
00: invalid
01: valid
00: disabled
10: 10 seconds
20: 20 seconds
30: 30 seconds
40: 40 seconds
50: 50 seconds
60: 60 seconds
71
GMV5 INDOOR UNIT SERVICE MANUAL
Default Value
Remark
When there are master and slave
wired controllers and the
temperature sensor of wired
controller is used, only the
temperature sensor of the master
wired controller is used by default.
Note:
1) In automatic mode, the
03
environment temperature sensor
settings are invalid for a common
IDU but the setting value is
memorized.
2)The environment temperature
sensor settings are invalid for a
fresh-air IDU. The temperature
sensor of air return vent is used by
default.
Temperature
sensor of unit:
Press " " or " " to add or reduce
0° C; temperature
by 1° C.
sensor of wired
controller: 0° C
Press " " or " " to add or reduce
by 1° C.
The temperature sensor of unit and
Temperature
the temperature sensor of wired
sensor of unit: -
controller share the same corrected
2° C; temperature
value.
sensor of wired
In heating mode, corrected value of
controller: 0° C
temperature sensor of unit =
corrected value of temperature
sensor of wired controller - 2° C.
Press " " or " " to add or reduce
00
by 10%.
Select "01" and then press and
hold the "ENTER/CANCEL" button
to restore the factory settings for
00
user functions (factory setting
recovery fails if remote shielding is
valid).
Select "01" and then press and
hold the "ENTER/CANCEL" button
to restore the factory status for
00
engineering settings (factory setting
recovery fails if remote shielding is
valid).
It indicates the number of seconds
00
for enabling the low-level fan every
15 minutes.