Gree GMV-ND100L/A-T Service Manual page 89

Multi variable air conditioners indoor units
Hide thumbs Also See for GMV-ND100L/A-T:
Table of Contents

Advertisement

GREE
Setting Code
Project number settings of
P42
Preferential operation
P43
One-key project number
P44
setting query for IDU
One-key project number
P45
Accumulated time clearing
P46
for air filter cleaning
Prompt settings for air filter
P47
System conservation
n0
operation settings
n1
Defrosting period settings
n3
Forcible defrosting
A7
Silent function of ODU
Highest capacity output
n4
limitation settings
Setting Content
50: 50 seconds
60: 60 seconds
1-255
IDU
00: no preferential operation
settings
01: preferential operation
00: not displayed
01: displayed
00: invalid
reset for IDU
01: project number reset
00: not cleared
01: cleared
00: no cleaning prompt settings
10-39: The first digit indicates the pollution degree of the using place
and the second digit indicates the accumulated operating time of
IDU. The two digits are described as follows:
 Slight pollution: The first digit is "1". If the second digit is "0", it
indicates that the accumulated operating time is 5500 hours. The
accumulated operating time is added by 500 hours when the second
digit is increased by "1". When the second digit is "9", the
accumulated operating time is 10000 hours.
 Medium pollution: The first digit is "2". If the second digit is "0", it
cleaning
indicates that the accumulated operating time is 1400 hours. The
accumulated operating time is added by 400 hours when the second
digit is increased by "1". When the second digit is "9", the
accumulated operating time is 5000 hours.
 Heavy pollution: The first digit is "3". If the second digit is "0", it
indicates that the accumulated operating time is 100 hours. The
accumulated operating time is added by 100 hours when the second
digit is increased by "1". When the second digit is "9", the
accumulated operating time is 1000 hours.
00: comfortability preferred
01: conservation preferred
40: 40 minutes
50: 50 minutes
60: 60 minutes
00: no defrosting
01: forcible defrosting
00: no silent function
01-09: intelligent nighttime silent mode
10-12: forcible silent mode
08: highest energy consumption limitation being 80%
09: highest energy consumption limitation being 90%
10: no conservation limitation
GMV5 INDOOR UNIT SERVICE MANUAL
Setting Value
84