(1) Press and hold the "FUNCTION" button for five seconds. The temperature area displays "C00".
Continuously press the "MODE" button for three times, and then press and hold the "FUNCTION"
button for another five seconds to enter the wired controller engineering parameter setting
interface. The temperature area displays "P00".
(2) Select a parameter code by pressing "▲" or "▼". Press the "MODE" button to switch to
parameter value settings. The parameter value blinks. Adjust the parameter value by pressing
"▲" or "▼" and then press the "SWING/CANCEL" button to complete settings.
(3) Press the "SWING/CANCEL" button to return to the upper-level menu till quitting parameter
settings.
For the engineering parameter setting list of the XK79 wired controller, refer to the engineering setting
query list in XK46 engineering parameter settings.
Note: In parameter settings, the function of "SWING/CANCEL" on the XK79 wired controller is equivalent
to the function of "ENTER/CANCEL" on the XK46 wired controller.
GMV5 INDOOR UNIT SERVICE MANUAL
79