Piping Work Requirements - Gree GMV-144WM/B-U Owner's Manual

Hide thumbs Also See for GMV-144WM/B-U:
Table of Contents

Advertisement

3.2.5 Considering snow in outdoor unit installation

3.3 Piping Work Requirements

There should be no fall among outdoor modules. Refer to the table below for piping work
requirements.
Outer Diameter mm(in.)
Φ6.35(1/4)
Φ9.52(3/8)
Φ12.7(1/2)
Φ15.9(5/8)
Φ19.05(3/4)
Φ22.2(7/8)
Φ28.6(1-1/8)
Φ34.9(1-3/8)
Φ41.3(1-5/8)
Fig.3.2.11
R410A
Refrigerant System
Wall Thickness mm(in.)
≥0.8(1/32)
≥0.8(1/32)
≥0.8(1/32)
≥1.0(3/76)
≥1.0(3/76)
≥1.2(1/21)
≥1.2(1/21)
≥1.3(2/39)
≥1.5(1/17)
10
GMV DC Inverter VRF
Type
O
O
O
O
1/2H
1/2H
1/2H
1/2H
1/2H

Advertisement

Table of Contents
loading

Table of Contents