Retain This User Manual SAVE THESE INSTRUCTIONS: This manual contains important instructions which must be followed during the installation, operation, and maintenance of the FN2 Series UPS and batteries. Please read all instructions before operating this equipment and save this manual for future reference.
Page 6
AC mains supply is securely grounded. To ensure safety for a hard-wired UPS, the system must be installed by a licensed electrician. This UPS includes a Maintenance Bypass Switch. Please follow the procedures when installing or operating Maintenance Bypass Switch. FN2 Series OM480053 Rev.: C...
12 hours every 3 months by connecting the UPS to the utility supply. Repeat this procedure every month if the ambient temperature is above 25°C (77°F). Failure to follow this procedure can reduce battery life. Temperature: Storage Temperature Range: -10°C to 40°C (14°F to 104°F) • FN2 Series OM480053 Rev.: C...
12 inches away from the wall or other obstructions. Temperature: Operating Temperature Range: 0°C to 40°C (32°F to 104°F) • Humidity: 10% to 90% relative humidity, non-condensing • Altitude: 3280 ft (1000 m) • FN2 Series OM480053 Rev.: C...
Falcon Electric, Inc. Introduction Overview The FN2 Series On-line UPS System provides the highest level of protection against severe power fluctuations. The FN2 Series UPS continually regenerates new, AC power in pure sine wave for superior protection. This user manual provides basic information about the Falcon FN2 Series Uninterruptible Power Supply (UPS).
Auto Bypass Loop: When the UPS is overloaded or abnormal, the UPS will automatically switch the load to bypass power. q. Output EMI Filter: Eliminates magnetic interference from the UPS output and protects from interference caused by the load. FN2 Series OM480053 Rev.: C...
To file a claim for shipping damage or concealed damage: YOU MUST file with the carrier within 24 hours of receipt of the equipment; YOU MUST send a copy of the damage claim within 3 days to Falcon Electric, Inc. Box Contents The UPS system is shipped complete with all accessories required for operation.
Page 12
Installation & User Manual Falcon Electric, Inc. Accessories Kit: FN2 Series OM480053 Rev.: C...
CAN Bus Connection port for parallel function Communication Option Slot 1 Cooling Fan External Battery Connector Utility Input Breaker (CB1) Bypass Input Breaker (CB2, Dual input model only) E.P.O. (Emergency Power Off): Normally Open Contact (Default) RS232 Port FN2 Series OM480053 Rev.: C...
The software bundled with the UPS is compatible with many operating systems such as Windows 2000, XP, Server 2003, VISTA, Server 2008, Windows 7 and Windows 10. For other applications such as Novell NetWare, Unix, or Linux, please contact Falcon. USB Port Complies with USB version 1.0,1.5 Mbps...
Utility input abnormal Not Used Alarm Silent UPS Output overload Not Used UPS Alarm 3-Digit Measurement Emergency Power Off UPS Inverter Off INPUT + OFF UPS Abnormal Lock 3-Digit Measurement Selection Identification UPS Operation Flow Chart FN2 Series OM480053 Rev.: C...
UPS to the wall. 2. Do not block the air flow to the ventilation openings of the unit. 3. Ensure that the installation site is clear and allows enough workspace to access UPS. FN2 Series OM480053 Rev.: C...
Page 18
Installation & User Manual Falcon Electric, Inc. Accessory Installation FN2 Series OM480053 Rev.: C...
Page 23
Terminal 5 Terminal 6 120V 120V Ground Jumper L22, N11 & G3 Jumper to N11 (L2) Neutral Used (L1) *The 120Vac output must not be loaded more than 50% of maximum rated UPS output capacity. FN2 Series OM480053 Rev.: C...
Page 24
Output Configuration Table (120V) Terminal 1 Terminal 2 Terminal 3 Terminal 4 Terminal 5 Terminal 6 120V 120V Ground Jumper to N11 Jumper to L12 Jumper to N22 Jumper to N22 Jumper to L22 Used FN2 Series OM480053 Rev.: C...
Page 25
Output: Use #8 AWG, 90°C copper wire, TRQ: 10 IN LB (Output) Input: Use #4 AWG, 90°C copper wire, TRQ: 18 IN LB 62A (Input) 10KVA 50A (Output) Output: Use #6 AWG, 90°C copper wire, TRQ: 10 IN LB FN2 Series OM480053 Rev.: C...
N o t f o r t e l e c o m m u n i c a t i o n n e t w o r k Con n e ct Con n e ct toL oa d toUtility 8 to 10kVA System with Transformer Module FN2 Series OM480053 Rev.: C...
Page 28
C onnect C onnect B attery cable to Load to Utility B ypass Input D C B r e a k e r T o U P S B a t t e r y FN2 Series OM480053 Rev.: C...
UPS was successful, and the charger starts to charge the batteries. 4. Press the UPS On button for approximately three seconds. The buzzer sounds twice and the LCD display changes from figure B to figure C. FN2 Series OM480053 Rev.: C...
Page 30
7. Start-up operation of the UPS is now complete. Allow a minimum of 8 hours for the UPS to charge the internal batteries before powering a load. FN2 Series OM480053 Rev.: C...
Windows) figure T (Output Frequency Synchronization Window) figure U (Inverter Output Voltage) figure V1 (UPS Operation Mode) figure W (Output Voltage Micro Tune Value) figure X (UPS Id) figure Y (Parallel function status) figure Z (Battery cabinet/capacity setting). FN2 Series OM480053 Rev.: C...
Page 35
Installation & User Manual Falcon Electric, Inc. FN2 Series OM480053 Rev.: C...
Page 36
Figure T indicates the bypass frequency window of the Inverter Output. The acceptable setting values are ±3 Hz and ±1 Hz. c. Figure U indicates the acceptable Inverter Output Voltage. Possible values are 200, 208, 220, 230, or 240 VAC. FN2 Series OM480053 Rev.: C...
Page 37
The UPS will conduct a 10-second battery test, if passed, LCD will display figure E1. If the batteries are dead, the test will fail, and LCD will display figure E2 along with battery error code and alarm. This typically indicates the batteries must be replaced. FN2 Series OM480053 Rev.: C...
Page 38
Turn MBS knob counterclockwise to the “INV” (Inverter) position. c. Reinstall MBS cover. d. Press the On Button for approximately 3 seconds, UPS will emit 2 beeps. i. UPS will perform power on self-test, if passed UPS will return to normal operation. FN2 Series OM480053 Rev.: C...
The Inverter output will be turned off, and the output load will be supplied by the Bypass loop. The LCD will display figure B. b. Turn Off the Utility Input breaker. i. The UPS is now turned off. FN2 Series OM480053 Rev.: C...
Page 40
1. Verify Input / Output wiring. 2. Verify AC Input Source is within UPS acceptable voltage range. 3. If problems persist, reference the following table for possible conditions and solutions otherwise please contact Falcon Electric, Inc. Service Department. Error Code Description...
Page 41
Er21 connector or set UPS with ID=1. Bypass voltage present in CF50 / CF60 Er24 constant mode. Please contact Falcon Electric, Inc. for resolution. Other error codes, contact Falcon Er** Service Department for further assistance. FN2 Series OM480053 Rev.: C...
The depleted batteries or packs may be returned to the Falcon Service Center at the end user’s expense for recycling. Prior to returning the depleted batteries or packs, please contact the Falcon Service Center and obtain a Return Material Authorization (RMA) number.
The table below provides the typical battery service life during float / trickle charge. Ambient temperature greatly affects the overall battery life. Period Temperature Float Charge (Years) 25°C 77°F 40°C 2.275VDC / 104°F CELL 50°C 122°F FN2 Series OM480053 Rev.: C...
Installation & User Manual Falcon Electric, Inc. Battery Replacement REFERENCE SAFETY SECTION OF THIS MANUAL FOR ALL BATTERY SAFETY WARNINGS. FN2 Series OM480053 Rev.: C...
Falcon Electric, Inc. N+1 / Parallel Operation Up to (4) FN2 Series UPSs may be connected in parallel, to provide up to 24kVA capacity for 6kVA models and 40kVA capacity for 10kVA models. N+1 Parallel Redundant configuration allows a up to 4 UPSs of the same capacity to be connected in parallel onto a common output bus.
This option requires Bypass Line to be disabled internally. Please specify this option at • the time of order or contact Falcon Electric Service Department for details. • In constant frequency mode, the UPS output capacity is de-rated to 75% of its maximum capacity rating.
Installation & User Manual Falcon Electric, Inc. Specifications Electrical *For latest released version, please visit our website at falconups.com. FN2 Series OM480053 Rev.: C...
Falcon Electric, Inc. Service & Warranty Technical Support In the event your FN2 Series UPS requires service, or should any other technical support be required, call, fax or email Falcon Electric, Inc. Service Department. Falcon Electric, Inc. 5116 Azusa Canyon Road Irwindale, CA 91706 Service: 800.842.6940 ext.
Falcon with an RMA number. For defective product sold domestically, as defined above, returned within 30 days of shipment, Falcon will pay for the shipping costs to and from its service center. For a defective product returned after 30 days but within 90 days of shipment, Falcon will only pay for shipping costs in sending the new or repaired product back to the end-user.